Loading...
HomeMy WebLinkAboutRECORDS REQUEST - 1433 CALLE JOAQUIN - FIRE INSPECTION 10-23-2018INSPECTION WORKSHEET (FIRE-04735-2017) San Luis Obispo Cellphone: XXX-XXX-XXXX. Address: 990 Palm Case Number: Inspection Date: Inspector: Case Module: Inspection Status: Inspection Type: PLOCC-114512-2014 10/23/2018 Julianna Hutchinson Plan In Violation Fire Business Inspection Job Address:Parcel Number:1433 Calle Joaquin San Luis Obispo, CA 93405 053-151-026 Contact Type Company Name Name Tenant [Motel 6] Checklist Item Passed Comments F.E. Maintenance Due - Maintenance and required service intervals. (a) Fire extinguishers shall be subjected to maintenance annually as described in this chapter or immediately after use or when specifically indicated by an inspection or at the time of hydrostatic test. NO Service extinguishers that have lost their charge. Water heater room extinguisher last serviced in 2017. F.A. Annual Test Record Required - Testing frequency. Unless otherwise permitted by other sections of this Code, testing shall be performed in accordance with with the schedules in Table 14.4.5 or more often if required by the authority having jurisdiction. NO Provide a copy of your most recent fire alarm test report. EL. 30"X 78" Clearance around Electrical Panel - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches, the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. NO Maintain clear access to main electrical panel shut off. EL. Provide Cover Plates - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. NO Provide a cover for exposed wiring in guest laundry room. S.H. Clearance b/w Combustibles & Ignition Sources - Clearance from ignition sources. Clearance between ignition sources, such as luminaries, heaters, flame-producing devices and combustible materials, shall be maintained in an approved manner. NO Clean lint off of water heaters behind laundry room. S.H. Seismic Strapping/Maint./Repair Waterheaters - Protection from seismic damage. Water heaters shall be anchored or strapped to resist horizontal displacement due to earthquake motion. Strapping shall be at points within the upper one third and lower one third of its vertical dimensions. At the lower point, a minimum distance of 4 inches shall be maintained above the controls with the strapping. NO Provide approved seismic strapping for water heaters. A. General Inspection Comments - General Inspection Comments YES Continue to maintain smoke/CO detectors in each unit. A reinspection will be conducted in approximately 21 days. For any questions please contact this inspector at (805)431-2217 or by email at jhutchinson@slocity.org. Oct 23, 2018 Page (1) Hutchinson, Julianna (Inspector)