HomeMy WebLinkAbout1a. FIRE-3207-2019 Fire Dept. Plan Reivew (679 Monterey)FIRE DEPARTMENT PLAN REVIEW
PROJECT DESCRIPTION: RESIDENTIAL FIRE SPRINKLER SYSTEM-FIRST REVIEW.
PROPERTY OWNER: 1504 BROAD STREET, SAN LUIS OBISPO, CA 93401.
ADDRESS: 679 MONTEREY STREET, SAN LUIS OBISPO, CA 93401.
APPLICATION NUMBER: 3113-2019
PLANS EXAMINER: JASON BERES
PROJECT MANAGER: S&M FIRE PROTECTION.
DATE: 02/08/2019
City records indicate that the existing building on this
property is business occupancy, serviced by an existing
commercial fire sprinkler system.
A new residential dwelling unit has been proposed for this
property, as indicated by the Site Plan referenced on the fire
protection plans.
Based upon this information, please address the following items:
1) The fire sprinkler system proposed to be installed for this
residence has been designed per NFPA 13D standards, and it
appears to be supplied by a dedicated underground fire
sprinkler piping source, which also provides service to the
existing commercial fire sprinkler system.
Provide an underground water meter and water supply piping
source that is compliant with NFPA 13D, Section A.6.2(c)
Preferable Arrangement for Stand-Alone Piping Systems, or
design the residential fire sprinkler system in this building
to meet current NFPA 13 standards, including an underground
fire line designed in accordance with City Engineering
Standards No. 6530 and No. 6590.
Please coordinate further with the Construction
Superintendent assigned to this project, and provide
revision based upon the conditions noted above.
2)Provide the test date, test location, and the name of the
responsible party who provided the water supply information
used in the design of this fire protection system. If
available, show the location of any fire hydrants used to
provide water flow test data for this system. Provide revision
based upon the scope of work for this project.
3) If the residential fire sprinkler system proposed to be
installed in this residence will be designed to NFPA 13D
standards, then provide fire sprinkler coverage for the attic
compartment in accordance with the City Municipal Code
requirements. Provide revision based upon the scope of work
for this project.
.