HomeMy WebLinkAboutInspection Report_1125 Garden St.City of San Luis Obispo Fire Department 2160 Santa Barbara Avenue San Luis Obispo,CA 93401 805/781-7380 Occupant Name: Hotel Cerro Inspection Date: 2/24/2022 Address: 1125 Garden Street InspectionType: Annual Fire Business Inspection City: San Luis Obispo Inspected By: Jason Beres 805/594-8021 jberes@slocity.org Suite: Parcel/Tax ID #: 002-424-021 Insp.Result Location Code Set Code Fail 2019 California Fire Code CHAPTER 9 FIRE PROTECTION AND LIFE SAFETY SYSTEMS 903.1 -Automatic sprinkler system compliance Code Text: Automatic sprinkler systems shall comply with this section. Inspector Comments: Annual fire sprinkler inspection conducted 01/14/2022,License No.761360. Annual standpipe inspection conducted 01/14/2022,License No.761360. Note:Hydraulic calculations plates found missing on the fire sprinkler riser and class-I standpipe system.Recommend contacting the fire protection contractor associated with the design of these two fire protection systems to obtain to this information. Once hydraulic calculation plates have been obtained for each system,please install per current NFPA 13 Installation of Sprinkler System standards. Fail 2019 California Fire Code CHAPTER 10 MEANS OF EGRESS 1010.1.10 -Panic and fire exit hardware. Code Text: Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A occupancy,assembly area not classified as an assembly occupancy,E,I-2 or I-2.1 occupancies shall not be provided with a latch or lock other than panic hardware or fire exit hardware.For Group L occupancies see Section 453.6.3 of the California Building Code. Exceptions: 1.A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.1.9.4,Item 2. 2.Doors provided with panic hardware or fire exit hardware and serving a Group A occupancy shall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10. Electrical rooms with equipment rated 1,200-amperes or more and over 6 feet (1829 mm)wide,and that contain overcurrent devices,switching devices or control devices with exit or exit access doors,shall be equipped with panic hardware or fire exit hardware.The doors shall swing in the direction of egress travel. Inspector Comments: Interior hallway exit doors found installed without panic hardware in the following locations:Stair No.4 (2nd floor)and Stair No.2 (2nd and 3rd floor). Recommend contacting the project manager associated with the construction of this building and confirm that the exit door hardware (as noted above)has been installed as noted per City permit No.0844-2017. Inspector Comments: Annual fire sprinkler inspection conducted 01/14/2022,License No.761360. Annual standpipe inspection conducted 01/14/2022,License No.761360. Annual fire alarm inspection conducted 01/14/2022,License No.761360. Annual fire extinguisher maintenance conducted 10/2021,License No.13591 (multiple locations onsite). Initial inspection conducted on 02/18/2022 with hotel management.Follow-up inspection conducted on 02/24/2022 to inspect keys installed in knox-box and the repair of fire alarm control panel and main electrical room doors. Note:Hotel management directed to review hotel safety plan requirements as set forth by CFC 406.4.-CFC 406.4.6.Paperwork to be provided to hotel management during initial inspection (02/18/22). Note:As a general reminder outdoor LPG heating appliances should be located a minimum of five feet from combustible materials (i.e.outdoor umbrellas)CFC 603.4.1.13. Note:Hydraulic calculations plates found missing on the fire sprinkler riser and class-I standpipe system.Recommend contacting the fire protection contractor associated with the design of these two fire protection systems to obtain to this information. Once hydraulic calculation plates have been obtained for each system,please install per current NFPA 13 Installation of Sprinkler System standards. Note:Interior hallway exit doors found installed without panic hardware in the following locations:Stair No.4 (2nd floor)and Stair No.2 (2nd and 3rd floor). Recommend contacting the project manager associated with the construction of this building and confirm that the exit door hardware (as noted above)has been installed as noted per City permit No.0844-2017. Hotel management directed to address the following items prior to requesting a follow-up inspection for this business: 1)Install hydraulic calculation plates for the commercial fire sprinkler system.See comments noted above. 2)Address panic hardware installation for interior hallway exit doors.See comments noted above. Upon completion of these two items,please contact the SLOFD Inspection Line (805)783-7775 to coordinate a follow-up inspection for this business. Inspector will return on or after 3/24/2022 Thank you for your cooperation in keeping your business and our community safe!If you have any questions,please contact us at 805/783-7775. Inspector: Jason Beres,Fire Inspector III 2/24/2022 Ref:3016