HomeMy WebLinkAbout184 Suburban Fire violations2/28/24, 4:15 PM
Report
Occupant Name
Address:
City:
Suite:
Insp.
Result Location
Fail
Pass
Pass
Pass
Pass
Pass
Pass
Fail
City of San Luis Obispo
Fire Department
2160 Santa Barbara Avenue
San Luis Obispo, CA 93401
805/781-7380
SPICE HUNTER (DM)
184 Suburban Road
San Luis Obispo
Cade Set
Inspection Date:
InspectionType:
Inspected By:
Parcel/Tax ID #:
Code
6/9/2023
Annual Fire Business Inspection
Mattie Bliss
805/781-7383
mbliss@slocity.org
053-257-024
2019 California Fire Code
CHAPTER 1 SCOPE AND ADMINISTRATION 105.1.1 -Permits required.
Inspector Comments: Submit permit application through Building Department for construction of mezzanine and work
done to sprinkler system last year. Observed approximately 20 sprinkler heads added under mezzanine space and tied
into existing riser at SE corner of North warehouse.
2019 California Fire Code
CHAPTER 5 FIRE SERVICE FEATURES
2019 California Fire Code
CHAPTER 5 FIRE SERVICE FEATURES
2019 California Fire Code
CHAPTER 5 FIRE SERVICE FEATURES
503.3 - Fire Lane Marking
505.1 - Address identification.
506.1 - Key box required.
2019 California Fire Code 604.3 - Clearance around electrical service
CHAPTER 6 BUILDING SERVICES AND SYSTEMS equipment.
2019 California Fire Code 604.3.1 - Electrical labeling for firefighters
CHAPTER 6 BUILDING SERVICES AND SYSTEMS
2019 California Fire Code
CHAPTER 50 HAZARDOUS MATERIALS -
GENERAL PROVISIONS
2019 California Fire Code
CHAPTER 50 HAZARDOUS MATERIALS -
GENERAL PROVISIONS
5004.2.2 - Secondary containment for hazardous
material liquids and solids.
5003.4 - Safety Data Sheets.
Inspector Comments: Ensure SDSs are readily available on the premises. Include hydrogen peroxide sanitizer in SDS
binder. Review with employees where binder is stored.
Pass 2019 California Fire Code 5303.5 - Secure compressed gas cylinders.
CHAPTER 53 COMPRESSED GASES
Fail 2019 California Fire Code
CHAPTER 10 MEANS OF EGRESS
1008.2 - Exit signs and emergency lights must be
operational at all times.
Inspector Comments: Replace tritium exit signs in warehouses. One sign observed to be due for replacement before
2019. Properly dispose of waste signs. Contact manufacturer or licensed radioactive hazardous waste hauler.
2019 California Fire Code
Fail CHAPTER 32 HIGH -PILED COMBUSTIBLE 3204.1 - General.
STORAGE
https://www.mobile-eyes.com/MobileEyes3/TrackFire_Report__TabletReports.asp?Type=Full&IOI D=5624
1/2
2128/24, 4:15 PM
Report
Inspector Comments: Fire protection analysis records on file show NE corner of south warehouse is capable of storing
jars and some boxed finished food products, class II and class III commodities, respectively. Observed wood pallets,
pallets of unfilled plastic seasoning containers, in addition to finished food products stored in area today. Per facility
representative, commodities are constantly moving in warehouse area.
Store materials in accordance with existing warehouse storage layout or demonstrate with a current fire protection analysis
that storage is in compliance with Fire Code and the warehouse supplies adequate fire protection for types of commodities
stored.
2019 California Fire Code
Fail CHAPTER 32 HIGH -PILED COMBUSTIBLE 3206.10 -Aisles.
STORAGE
Inspector Comments: Observed pallets of materials and other stored items partially or completely blocking aisles in
south warehouse. Immediately begin clearing aisles in accordance with chapter 32 of CFC and the warehouse guidelines
submitted by Fulton Fire Engineering Inc.
Inspector Comments: Empty lot adjacent to Tank Farm Rd was mowed prior to June 1; however, weeds are returning and will need
abatement.
One emergency exit flood light failed to illuminate when tested in upstairs office area. Repair/replace.
Racks throughout both warehouses do not appear to be bolted or strapped. Secure high piled storage racks in accordance with fire
and building code.
Inspector will return on or after 7/17/2023
Thank you for your cooperation in keeping your business and our community safe! If you have any
questions, please contact us at 805/783-7775.
Company
Representative:
- ra relict mIY in moLileeyea daumenls
Ken Kreyenhagen
6/9/2023
Inspector:
"tignawre valitl mly in mobileeyas documents
Mattie Bliss
6/9/2023
Ref: 5624
https://www.mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Type=Full&1OID=5624 2/2
2/28/24, 4:15 PM
Report
City of San Luis Obispo
Occupant Name: SPICE HUNTER (DM)
Address: 184 Suburban Road
City: San Luis Obispo
Suite:
Insp, Location Code Set
Result
Fail -
Cleared
Fail
Fail -
Cleared
Fail -
Cleared
Fire Department
2160 Santa Barbara Avenue
San Luis Obispo, CA 93401
805/781-7380
Inspection Date: 7/26/2023 (Initial Insp. Date: 6/9/2023)
InspectionType: Reinspection #1 (Annual Fire Business Inspection)
Inspected By: Mattie Bliss
805/781-7383
mbliss@slocity.org
Parcel/Tax ID #: 053-257-024
2019 California Fire Code
CHAPTER 50 HAZARDOUS MATERIALS -
GENERAL PROVISIONS
JCleared on 7/26/2023
5003.4 - Safety Data Sheets.
Inspector Comments: Place SDS for Oxonia Active into designated binder.
2019 California Fire Code
CHAPTER 1 SCOPE AND ADMINISTRATION
2019 California Fire Code
CHAPTER 32 HIGH -PILED COMBUSTIBLE
STORAGE
2019 California Fire Code
CHAPTER 10 MEANS OF EGRESS
V Cleared on 712612023
2019 California Fire Code
CHAPTER 32 HIGH -PILED COMBUSTIBLE
STORAGE
VC/eared on 712612023
105.1.1 - Permits required.
3204.1 - General.
1008.2 - Exit signs and emergency lights must be
operational at all times.
3206.10 - Aisles.
Inspector Comments: Submit written Respiratory Protection Program to mbliss@slocity.org. Observed facility employees wearing
surgical masks while working near equipment filling chili -lime seasoning. Per facility representative, surgical masks are optional PPE.
These operations resulted in a respiratory reaction (coughing, sneezing) for myself, another city inspector, and other facility personnel
when walking through the manufacturing areas. Provide dust hazard study/analysis for dust producing operations.
Submit permit through City Building Department for rack storage.
Inspector will return on or after 8/28/2023
Thank you for your cooperation in keeping your business and our community safe! If you have any
questions, please contact us at 805/783-7775.
Ref: 5624-5789
https://www.mobile-eyes.com/MobileEyes3fTrackFire_Report_TabletReports.asp?Type=Full&]OID=5789 1/1