MBMORANDUM
To:
Date:1
From:
Hal
Subject: Graphic
Bill Mitchell, the superin
block structure that he is
you will want to route it
a copy of the plan check
1997
G. Hanson, Fire
to
All that we are looking for
the driveway entrance (in words
as long as it is
between 4'-6" and 6'
Mr. Mitchell's
Building Permit Coordinator
Panel S Broad Street, Marigold Center
Center, faxed me a copy of the concrete split faced
the graphic annunicator panel (GAP). I'm sure that
Planning , and Building/Grading. We included
t to you for the fire-alarm system.
face northerly, be supported substantiallY, and be close to
do not have any opinion as to what the structure looks like
visible)., our GAP Standard requires the GAP to be located
so as to be visib first arriving emergency personnel.
number, fax number it shown on the first page
05/01/s? TIIU 14:49 FAX 8057828809 CHQ @ ITARIGOLD @ oor
CHg lrucrlic II, Inc"
rtInrigold Center - 0n ,\ile Ollitt
399il llroail Slreel r $'grr l.uis Ohislto, (',,1 9"1401
0s 782-8800 t I:rlX 80s 78)-,Y809
llA'l'li: May1,1gg7 't.lt\ili sliN'l':3:55pm
T-O:Ron Hanson Frlx NLtNllt lt: s43-8019
lillt[l: city of SLo - FIRE DEPT.lltAil, 0lil(J.?: No
Flt(|lll: Birt Mitchetl 't'(t'l'AL I,AGtis: * 4
(lnchrrling llris cover page)
ITIi:
To follow is the location of Annuciator
O5/OI/97 THU 14:50 FAX 805?828809 CIIQ @ MARIGOLD rg 002
,)
Inlrstrtal V'la
/
tr
a'(\
F
$r
*t:
\$s
r-t
orh
s-:r
ci
\
I
05/01/e? THU 14:51 FAX 805?828809 @a @ oos
a a
,, gl
ttq6lh
SAW CUTTI}IG, BREAKING, DRIILING ANO NEMOVAT
s heet natr I {'tesh r n
X
y^t
*A"
L ,'
hnnordtat' SiXn
f"J istal $o' firru*cirt'P,
f,t';u , Jlu -rl
lr
s J-{
a
J' z-- -.-'l'3
. Lo$. San
a
{7titl ttz.el$o
lflgl321-01$(ilrf irr-3810
Cornlt: ll05l l;Z'llBS!
. San tcandro: {{15} t5t'8010
. Escondldo: l8l9l f89'1014
r San Dlego: 16191 203-720t1
r Senll Clrm: {{08f gt0'9l9il
r San Fernendo Velley: (tl81 504'0033
Construr:lion Sat vices Divisiot
I (sr8t 380-r5r9
- 05/0t/97 TIIU 14:52 FAx 8057828809 & 004
sAw curill{G,BREAKIITIG, DRITLING AND REII/IOVAI
l'-o" --.--
l ,,rrrlrrrt lion Setvices Division
-l
I
rlri
I
/1
s
Split ld BI otlq
h
e
I
\ntt rtCtat
nt
I
. lAnahelm: l7t{l ttt-tl6o. Los Angchr: l2ltl l2l-Ol3l
r San Bfinrrdlnc (?lll t?t-3880
, Jenluru Counly: Goll lt2-!834
r Saeremrnto: (9101 StGlStg
l'..lt.Lt
r Sen Leandro: 14l5l 35t.8U10. Eseondldo: (B19| 189-1014
' San Dlego: 16191 2e3-726t1
r Senla Clara: 14081 970-9494
r San Fernando Volley: GlE, 504-0033
r.r .1 I r b a - Lu.L r-tl!
frnryh 3r ale j
FIRE DEPARTMENT PLAN CHECK - FIRE ALARM
SUBJECT:
OWNER:
ADDRESS:
JOB NUMBER:
DATE ROUTED:
DATE COMP.:
PLAN CHECKER:
PROJ. MANGR.:
Fire Alarm System for all of the Buildings in the Marigold Center
Marigold Ventures
3950 Broad - Main File for Site
97-025 PLAN CHECK #1
Feb. 11,1997
Feb. 27, 1997 (11 working daYs)
Ronald G. Hanson, Fire lnspector/Plan checker (805) 781-7379
Marion Todd, Ph# 541-4470 SHEET 1 OF 5
ptans submitted have been reviewed for compliance with the appropriate standards as indicated
below. Unless otherwise noted, all code references are from the current editions of the appropriate
codes. Devices installed must comply with minimum NFPA and UFC requirements' ADA
requirements have not been review by the Fire Department. The applicant is advised
to investigate any additional ADA requirements which may be required.
1) provide record drawings and certification of the fire alarm system in accordance
with NFPA 72, Sec. 1.7.2 prior to final approval'
2l All signals shall be monitored by a UL listed monitoring station. lf Valley Alarm
is used they must monitor tamper and trouble signals also'
3) Please revise voltage drop and battery calculations to show all proposed
devices.
4l Submit cut sheets for all devices, wiring, and appliances proposed or used'
provide Ul-listing and CSFM approvals. The following items need to be
included this submittal; rate of rise heat detector, HVAC duct detection, tamper
devices for os&Y valves, wiring, graphic annunciator panel (type of panel &
pedestal), key pad (D1256), dual phone modula (D928 or D12Bl, & the
monitoring equipment used for class-1 hoods'
b) The owner shall hire a qualified agency to provide maintenance inspections as
required by NFpA 72 and UFC on at least a quarterly basis. Please provide a
maintenance contract for our files. All devices within the complex shall be
reviewed within a Years time.
ZI
Sheet 2 ot 5
135O Broad Street
General File - Fire Alarm for Marigold Center
PC#97-025.pc1
6)Alarm Signal - The alarm signal shall be keyed to one half to one second "on"
and one
-second "off" for three cycles. The alarm signal shall be_ repeated for
the duration that the fire alarm system is activated. IUFC 1007.3.3.3.21
Connections to Other Systems - A fire alarm system shall not be used for any
p*p*" "th"r tn.n tire warning unless approved by the authority having
jurisdiction. IUFC 1 007.3.3.4a1
Supervision - Means of interconnection equipment, devices and appliances shall
br r"prt"ired for the integrity of the interconnecting conductors or equivalent,
as set forth in UFC Standard 1O-2.
a. Show how the external power supply is wired into the FACP.
Provide the following information on the single line (riser) diagram':
8).
9)
Conductor information, including size, stranding, insulation type, etc
ICEC, Article 7601
Conduit fill calculation or NEC reference. [CEC, Table #4]
Location of end-of-line devices. t1994 UFC, 1O01 '31
lnclude zone descriPtions.
1O). All required fire detection systems installed within the jurisdiction shall be
supervised by a central station listed by Underwriters Laboratories for receiving
fire alarms.
d provide a U.L. "Central Station Signaling System Certificate" for Valley
Atarms. tuFc 1007.3.3.6.1 as amended by M.C. 15.08.2701
11)Annunciation -
a. Each building shall be considered as a separate zone.
b. Each device within each building shall be considered a separate zone
within that building.
As a minimum the following zones snali Oe represented for each building
weather used or not.
1. pull Station - There should only be one pull station for each
a
b
c
d
building since this is not a evacuation system'
Sheet 3 of 5
1350 Broad Street
General File - Fire Alarm for Marigold Center
PC# 97-O25.pc1
2. HVAC Duct Detection - provide an LED display for each HVAC
unit showing the status of the smoke detector. lnclude testing
and alarm verification.
3. Class-1 Hood - provide monitoring for each hoods suppression
system. tnclude Separate zone if more than one business' Ok to
place several hoods at the same business on one zone if
necessary.
4.WaterFlow-Thereshouldonlybeonepullstationforeach
building'
S. PIV Timper - Each valve tamper shall be a separate zone
indicating which building it serves'
6. Smoke/Heat Detection - Zone by building'
7. Area separation walls - smokes are used for door hold open and
are "uriently
proposed for the one-hour area separation wall at
sav-on Drug' and will release roll down doors. lf used in
conjunction *itn the required area separation wall (for the High
Rack storage areas) they shall be on a separate zone. lf used in
just to hold open doors not in conjunction with an area separation
wall they may be on the same zone as smoke/Heat Detection'
5. os&Y - Tamper alarms shall be identified as a separate zone'
Graphic Annunciator Panel / Remote Panel - Remote annunciator panels shall
meet the requirements of UFC Section 1007.3'3.7a and shall be electrically
supervised. IUFC 1007.3'3.7.11
13) Acceotance Test and Certification -
a. Acceptance Test - Upon completion of the installation, a satisfactory test
of the entire system shall be made in the presence oJ the chief' All
functions of the system or alteration shall be tested. IUFC 1OO7'3'4'1)
b. Certification - The permittee shall provide the NFPA Certification of the
Compliance to the chief that the system has been installed in accordance
with the approved plans and specifications. tuFC 1007 '3'4'21
lnstructions - When required by the chief, operating, testing and
maintenance instructions and "as-built" drawings and equipment
specification s shall be provided at an approved locations' tUFC
1007.3,4.31
12l,
c
15)
Sheet 4 of 5
1350 Broad Street
General File - Fire Alarm for Marigold Center
PC# 97-O25.Pc1
14l,provide a written description or matrix chart to define the events which occur
when various initiating devices are activated. The description should include
details relating to annunciation, evacuation warning, remote signaling and
activation of fire safety control functions, as applicable'
Part 3 of Title 24 CCR, The California Electrical Code (CEC) limits the amount of
conduit fill to a maximum of 4Oo/o. Chapter 9 or Part 3 provides tables
indicating the maximum number of conductors of various sizes which can be
used in various sizes of conduit in order to comply with the 40% limitation.
Sh.ow the size of conduit and the percentage of conduit file. lnclude
caiculations for review and approval or table number from NEC.
16) Show the following administrative
1001.31:
requirements on the plans t1994 UFC,
lnstalling contractors name, address and phone number'
Contractors license & local business license numbers'
site address - 3950 Broad is the is the General File for the entire
complex.
Basis for system installation - Show the Building Code occupancy
classification for each building'
Building owner and tenant name (if already established).
Location of all components, including end-of-line devices, if involved.
11994 UFC, 1001 .31
Symbol legend which includes quantity of devices, manufactures name,
model, etc. t1994 UFC, 1001 .31
Description of zone assignments/device addresses. t1994 UFC, 1001'31
Provide a complete building cross section, include attic, soffit, or ceiling
details with each individual building submittal. t1994 UFC, 1001'31
Specifications and details of through-penetration fire stopping, if
required. [U.L. Fire Resistance Directories]
Device mounting heights for manual boxes and visible notification
appliances. TNFPA 72, 3-8.1.1,5-9.1.1 & 6-4.1.11
Primary power supply details. TNFPA 72, 1-5'2.4,'2'81
171 provide the signals/wording that will be received by the central station.
1g) Show the actual wording that will be used on the key pad. lnclude device
name and address number'
a.
b.
c.
d.
e.
f.
g.
h.
i.
k
t.
-l
Sheet 5 of 5
1350 Broad Street
General File - Fire Alarm for Marigold Center
PC# 97-O25.pc1
19) Missing PlV, water flow, and tamper for Building E. lnclude HVAC, and smoke
release for doors.
2Ol Missing HVAC system for Building G.
21l' Missing class-l hoods (three total) for Carl's Jr., Building pad C.
221 Missing HVAC systems for Vons, Building A.
23!. lnclude information on how the batteries will be supervised at the separate
power supply used for the horns at the pull stations.
It appears as if the wiring for the horns is supervised by the module
supplied in the Radionics panel. The batteries in the Radionics panel also
appear to be supervised but not the aux. power supply.