HomeMy WebLinkAboutBLDG-2289-2020_Review_V1
Date: December 18, 2020
Plan Check Review # 1
Staff Response: Review #1 Review #2 Review #3 Review #4 (Additional Fees)
Applicant Response:
Please indicate here if any new changes have been made to the plans that are not a result of the corrections from
this list. Briefly describe the type of changes and their location on the plans.
Check one: _____yes ______no
Print Name:
If yes, please briefly describe the changes and where they are located on the plans:
Project Address 1150 Laurel Ln.
Project Name Warehouse Remedial Work/ Code Compliance Work
Application Number BLDG-2289-2020
Review of Plans
Occupancy Class B/S-1
Construction Type III-B
Occupant Load Must Be Provided
Sprinklers NFPA-13
1 2 3 4
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 2
Building
Lizzandro Diaz
ldiaz@slocity.org P: 805-781-7157
☐ Ready for Action ☒ Needs Resubmit ☐ OK for Counter Re-Check
☐ Final Inspection Required (staff reminder: add yourself to final inspection in permit module)
1. Permit valuation shall include total value of work, including materials and labor, for which the permit is
being issued, such as electrical, gas, mechanical, plumbing equipment and permanent systems.
2. When the adjusted construction cost, as defined, is less than or equal to the current valuation threshold,
as defined, the cost of compliance with Section 11B-202.4 shall be limited to 20 percent of the adjusted
construction cost of alterations, structural repairs or additions. When the cost of full compliance with
Section 11B-202.4 would exceed 20 percent, compliance shall be provided to the greatest extent
possible without exceeding 20 percent. §11B-202.4
3. Where a building contains two or more occupancies, the means of egress requirements shall apply to
each portion of the building based on the occupancy of that space. Where two or more occupancies
utilize portions of the same means of egress system, those egress components shall meet the more
stringent requirements of all occupancies that are served. (1004.4 Multiple Occupancies)
4. The means of egress serving a room or space shall be illuminated at all times that the room or space is
occupied. (1008.2 Illumination Required)
5. In the event of power supply failure in buildings that require two or more means of egress, an
emergency electrical system shall automatically illuminate all of the following areas:
1.Interior exit access stairways and ramps.
2.Interior and exterior exit stairways and ramps.
3.Exit passageways.
4.Vestibules and areas on the level of discharge used for exit discharge in accordance with
Section 1028.1.
5.Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the
exit discharge. (1008.3.2 Buildings)
6. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except
where such adjoining rooms or areas and the area served are accessory to one or the other, are not a
Group H occupancy and provide a discernible path of egress travel to an exit.
7. If an area has been altered without providing an accessible path of travel to that area, and subsequent
alterations of that area or a different area on the same path of travel are undertaken within three years of
the original alteration, the total cost of alterations to the areas on that path of travel during the preceding
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 3
three-year period shall be considered in determining whether the cost of making that path of travel
accessible is disproportionate. (11B-202.4 Path of Travel Requirements in Alterations, Additions and
Structural Repairs)
8. Adjusted construction cost of alterations, structural repairs or additions does not include the cost of
alterations to path of travel elements. §11B-202.4
9. At least one accessible route shall connect accessible building or facility entrances with all accessible
spaces and elements within the building or facility, including mezzanines, which are otherwise
connected by a circulation path. §11B- 206.2.4 (See exceptions 1 through 7)
10. Accessible routes shall coincide with or be located in the same area as general circulation paths. Where
circulation paths are interior, required accessible routes shall also be interior; An accessible route shall
not pass through kitchens, storage rooms, restrooms, closets or other spaces used for similar purposes,
except as permitted by Chapter 10. §11B-206.3
11. At least one accessible route shall be provided within the site from accessible parking spaces and
accessible passenger loading zones; public streets and sidewalks; and public transportation stops to the
accessible building or facility entrance they serve. Where more than one route is provided, all routes
must be accessible. §11B-206.2.1 (See exceptions)
12. A curb or wheel stop shall be provided if required to prevent encroachment of vehicles over the required
clear width of adjacent accessible routes. §11B- 502.7.2
13. Provide occupant load on Title page A0.00 under Project Statistics.
14. Provide the use of each area. The name of the business does not help identify the occupancy. What type
of business is HAPTX, CODA, ACORN etc.
15. Show travel distance on plans for both floors. The maximum travel distance from any accessible space
to an area of refuge shall not exceed the exit access travel distance permitted for the occupancy in
accordance with Section 1017.1. (1009.6.1 Travel Distance)
16. Exit access travel distance shall not exceed the values given in Table 1017.2.
17. Show all doors for each area. Provide a door schedule.
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 4
18. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not
less than one accessible means of egress. Where more than one means of egress is required by Section
1006.2 or 1006.3 from any accessible space, each accessible portion of the space shall be served by
accessible means of egress in at least the same number as required by Sections 1006.2 or 1006.3. In
addition to the requirements of this chapter, means of egress, which provide access to, or egress from,
buildings for persons with disabilities, shall also comply with the requirements of Chapter 11B as
applicable. (1009.1 Accessible Means of Egress Required)
19. Accessible routes shall coincide with or be located in the same area as general circulation paths. Where
circulation paths are interior, required accessible routes shall also be interior. An accessible route shall
not pass through kitchens, storage rooms, restrooms, closets or other spaces used for similar purposes,
except as permitted by Chapter 10.
20. Provide a door schedule for Lobby 1.
21. Exterior exit doors shall lead directly to the exit discharge or the public way. Show all North doors of
building as egress doors to the Public Way. (1022.2.2 Arrangement)
22. Where occupants egress from one or more rooms, areas or spaces through others, the design occupant
load shall be the combined occupant load of interconnected accessory or intervening spaces. Design of
egress path capacity shall be based on the cumulative portion of occupant loads of all rooms, areas or
spaces to that point along the path of egress travel. (1004.2.1 Intervening Spaces or Accessory Areas)
23. Where the means of egress from stories above and below converge at an intermediate level, the capacity
of the means of egress from the point of convergence shall be not less than the largest minimum width
or the sum of the required capacities for the stairways or ramps serving the two adjacent stories,
whichever is larger. (1005.6 Egress Convergence)
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Response (Include Sheet and Detail Number):
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 5
Engineering Development Review- Public Works
Richard Avila
ravila@slocity.org Phone (805) 783-7734
☐ Ready for Action ☒ Needs Resubmit ☐ OK for Counter Re-Check
☒ Final Inspection Required (staff reminder: add yourself to final inspection in permit module)
General Comments:
Provide responses to each comment, as appropriate, and note on what page(s) in the plan set each item is
addressed. Include the name and phone # of the person(s) providing responses.
The following items need correction on the draft construction plans :
1. See plans labeled “Public Works Dev Rev Redlines #1”. Return this redlined set with your
resubmittal.
2. The following notes shall be included on the cover sheet of the building plans, the architectural site
plan, and/or grading plans as appropriate:
a. All work located within the public right-of-way or within the jurisdiction of the Utilities and
Public Works Departments shall comply with the most current edition of the Engineering
Standards and Standard Specification. (The current adopted Standards are dated August 2020.)
b. Any sections of damaged or displaced curb, gutter & sidewalk, or driveway approach shall be
repaired or replaced to the satisfaction of the Public Works Director.
c. A separate encroachment permit is required for any work in the public right-of-way, within city
easements, or for connections to public utilities. Work requiring an encroachment permit
includes but is not limited to demolitions, utilities, water, sewer, and fire service laterals, curb,
gutter, and sidewalk, driveway approaches, sidewalk underdrains, storm drain improvements,
street tree planting or pruning, curb ramps, street paving, and pedestrian protection or
construction staging in the right-of-way.
d. Contact the Public Works inspection hotline at 781-7554 with at least a 48-hour notice for any
required encroachment permit inspection or final inspection.
e. The adjoining street shall be cleaned by sweeping to remove dirt, dust, mud and construction
debris at the end of each day.
f. A traffic and pedestrian control plan shall be submitted to the Public Works Department for
review and approval prior to encroachment permit issuance.
g. Any existing survey monuments shall be protected in place or shall be tied out by a licensed land
surveyor prior to disturbance and then replaced prior to occupancy in accordance with Section
8771 of the California Business and Professions Code.
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 6
h. Erosion control measures shall be implemented and maintained to the satisfaction of the Building
Official and Public Works Director during all demolitions, construction and ground disturbing
activities.
i. Hand digging is required within the drip line of trees to remain; any exposed roots shall be observed
by City Arborist before removing. Contact City Arborist Ron Combs at 781-7023 before
commencing with construction, grading, or excavations.
j. One 15-gallon street tree is required for each 35 lineal feet of frontage or fraction thereof. Tree
species and planting requirements shall be per city engineering standards.
3. Indicate or label the width, paint type and color at the new crosswalk. Sheet A2.00
4. Plans reference civil, electrical and landscaping plans. Add a notation on the sheet that, “This Sheet
is for Reference Only”.
Fees
Vanessa Nichols
vnichols@slocity.org Phone (805) 781-7588
☐ Ready for Action ☒ Needs Resubmit ☐ OK for Counter Re-Check
☐ Final Inspection Required (staff reminder: add yourself to final inspection in permit module)
1. Final fees pending other department reviews. No action required.
Plan Check Review #1
1150 Laurel Ln.
BLDG-2289-2020
Page 7
FIRE DEPARTMENT PLAN REVIEW
PROJECT DESCRIPTION: WAREHOUSE CODE COMPLIANCE
PROPERTY OWNER:
ADDRESS: 1150 LAUREL
APPLICATION NUMBER: BLDG-2289-2020
PLANS EXAMINER: RODGER MAGGIO
PROJECT MANAGER:
DATE: 12/03/20
Your plans are being returned to you for corrections. To expedite the re-check process, please note on this list (or
a copy) where each correction item has been addressed, (i.e.; indicate the sheet number, note number, or copy of
page in specifications that is referenced). Be sure to enclose the marked-up list when you submit the revised
plans.
1. Suite 110 has applied for a sprinkler permit to accommodate high-piled storage of aerosols, and a building permit
for a high-piled storage racking system. Please rectify with the tenant and provide a list of commodities stored at
the location.
2. While the martial arts studio is a Group B occupancy, and while Chapter 5 of the building code does not require
separation between a Group B and an S1 occupancy, it is an anomaly in the code as Chapter 10 does not permit a
group B occupancy to exit through a storage occupancy unless the B occupancy is ancillary to the warehouse (ie;
breakroom, or office space for warehouse staff). The martial arts space shall either have a direct exit discharge to
the public way or have a exit directly to an exit access corridor without passing through the warehouse.