Loading...
HomeMy WebLinkAboutARCH-0188-2023 20230420 (Laurel Garden) - Utility LinesJ608 9699 526883 3711 5083 T0734 69708 509598 737484 648130 905034 188530 770146 926954 T730073 T128631 TO SSD SWITCH 4817 14275 9699 M 526883 LEGEND EXISTING DESCRIPTIONINSTALL PRIMARY CABLE: 2-1/0AL EPR 25kV IN NEW 1-4" CONDUIT SERVICE CABLE:4 RUN(S) OF 1,000A QPX IN 4 OF 7 - 5" CONDUITS NOTES:09-18-13 14.APPLICANT TO PROVIDE ADEQUATE P.U.E'S AND/OR ROW'S FOR PG&E FACILITIES. ANY ADDITIONAL REQUIRED RIGHTS OF WAY ARE TO BE SURVEYED AND DOCUMENTED BY PG&E AT THE APPLICANT'S EXPENSE. CONDUIT, TRENCHING, AND BACKFILL: 1.ALL DIMENSIONS AND LOCATIONS ARE ESTIMATED, APPROXIMATE AND MAY BE SUPERSEDED BY A JOINT TRENCH DRAWING. REFER TO THE JOINT TRENCH COMPOSITE DRAWING FOR EXACT TRENCH LOCATION 2.MAINTAIN MAXIMUM PRACTICABLE HORIZONTAL CLEARANCE BETWEEN PG&E FACILITIES AND "WET" UTILITIES (WATER, SEWER, STORM DRAIN, ETC.). THE MIN. ALLOWABLE SEPARATION BETWEEN PG&E FACILITIES AND ANY PARALLEL "WET" UTILITY IS 3/FT. WITH A PRESENCE OF 1/FT. OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE BARRIER. THIS MEASUREMENT IS BETWEEN THE OUTER EDGE OF THE PG&E FACILITY AND THE OUTER EDGE OF THE PARALLEL "WET" FACILITY. IF 3/FT. CANNOT BE MAINTAINED, A FORMAL VARIANCE MUST BE OBTAINED FROM PG&E WORK WITH THE PG&E INSPECTOR (REFERENCE PG&E UO STANDARD S5453). 3.BOX, PAD, AND CONDUIT SIZES AND LOCATIONS SHALL CONFORM TO THE PG&E ELECTRIC CONSTRUCTION DRAWING. 4.PROVIDE LONG CONDUIT SWEEPS WHERE INDICATED. RECOMMENDED SWEEP RADIUS (10' OF RADIUS PER INCH OF CONDUIT DIAMETER) EXAMPLE: 4" CONDUIT = 40' RADIUS 5.DO NOT EXCEED 300 DEGREES OF BENDS IN ANY CONDUIT RUN (INCLUDING FEED LOCATION). NOTE: SECONDARY AND SERVICE RUNS OF 200 FEET OR LESS MAY HAVE UP TO 315 DEGREES OF BENDS (REFERENCE PG&E DOCUMENT 038193, REV. 7, DATED 6-28-13). 6.MANUFACTURED BENDS OR APPLICATION OF HEAT SHALL NOT BE USED TO OBTAIN LONG CONDUIT SWEEPS. 7.ALL CONDUITS SHALL BE PROVEN AND A POLYESTER PULLING TAPE INSTALLED. 8.MANUFACTURED BENDS ARE NOT TO BE CUT, SHORTENED, OR ALTERED IN ANY WAY. 9.IDENTIFY ENDS OF BURIED CONDUIT WITH AN ELECTRONIC MARKER AND A VERTICAL CONDUIT SCRAP INSTALLED FROM RIGID CAP TO GROUND LEVEL. 10.CONDUITS ENTERING PRIMARY BOXES SHALL BE AT A RIGHT ANGLE TO THE WINDOW OR WALL. 11.STUB CONDUITS AT RISER POLES IN QUADRANTS AS SHOWN. AT IDENTIFIED POLE LOCATIONS, THE TRENCHING AGENT IS TO EXCAVATE TO TRENCH DEPTH AND INSTALL A 30" DIAMETER CARDBOARD TUBE. THE RISER CONDUIT BEND IS TO BE PLACED OUTSIDE AND ADJACENT TO THE TUBE AT THE POLE QUADRANT INDICATED. BACKFILL AROUND AND INSIDE TUBE WITH CLEAN NATIVE FILL. 12.LS2 STREET LIGHT CONDUIT GOING TO PG&E BOXES OR PEDESTALS NOT DESIGNATED AS P.O.S. (INCLUDING TRANSFORMERS) WILL NOT BE ACCEPTED OR CONNECTED. 13.ONLY ONE LS2 STREET LIGHT (P.O.S.) CONNECTION PER BOX OR PEDESTAL. 15.CALL 811 (UNDERGROUND SERVICE ALERT) 48 HOURS PRIOR TO EXCAVATION FOR UNDERGROUND UTILITY LOCATION MARKING. 16.48 HOUR NOTICE REQUIRED FOR UNDERGROUND INSPECTION. 17.MATERIALS AND WORKMANSHIP SHALL BE FIRST QUALITY IN EVERY RESPECT, PLUMB AND TRUE, AND ACCORDING TO THE SPECIFIC REQUIREMENTS OF THE DRAWINGS AND THE ABOVE APPLICABLE NOTES AND SPECIFICATIONS. 18.THE APPLICANT IS TO VERIFY ALL PROPOSED INSTALLATIONS, CONDITIONS & SPECIFICATIONS PRIOR TO COMMENCING WITH ANY PORTION OF WORK. ANY DISCREPANCIES, DELETIONS OR INCONSISTENCIES ARE TO BE REPORTED TO THE PG&E REPRESENTATIVE IMMEDIATELY. THE APPLICANT SHALL COMPLY WITH ALL APPLICABLE SPECIFICATIONS. ANY VARIATIONS FROM PLANS OR SPECIFICATIONS RELIEVES PG&E OF ALL RESPONSIBILITY FOR THE SUBSTRUCTURE OR DESIGN. REFER TO ELECTRIC & GAS SERVICE REQUIREMENTS (GREEN BOOK) OR SEPARATE PG&E STANDARD DRAWINGS. CONTACT YOUR PG&E REPRESENTATIVE FOR COPIES, OR ACCESS. WWW.PGE.COM/GREENBOOK LAND RIGHTS AND EASEMENTS: SAFETY AND WORKMANSHIP: SERVICE CABLE:6 RUN(S) OF 1,000A QPX IN 6 OF 7 - 5" CONDUITS PRIMARY CABLE: 3-1/0AL EPR 25kV IN NEW 1-4" CONDUIT PRIMARY CABLE: 3-1100AL EPR 25kV IN NEW 1-6" CONDUIT VACANT CONDUIT: 1-4" VACANT CONDUIT:1-6" & 1-4" JOINTLY OWNED POLE - SIZE AS SHOWN RISER OVERHEAD SWITCH FUSED CUTOUTS | DISCONNECTS PMI-9TT PADMOUNTED TRANSFORMER - SIZE AS SHOWN 3' x 5' x 3'6" PRIMARY ENCLOSURE METER WORK AGENT RESPONSIBILITIES TO PERFORM ALL TRENCHING AND EXCAVATION TO PERFORM JOINT TRENCH COMPOSITE | FORM B TO PERFORM ALL POLE WORK TO PERFORM ALL TIE-IN WORK TO INSTALL ELECTRIC DISTRIBUTION AND SERVICE FACILITIES. CABLE, TRANSFORMERS, INTERRUPTERS, ETC.PG&E TO INSTALL ELECTRIC DISTRIBUTION AND SERVICE SUBSTRUCTURES. CONDUIT, ENCLOSURES, PADS, BOXES, ETC.APPLICANT APPLICANT PG&E PG&E PG&E M PRIMARY METER REMOVAL OF FACILITIES OVERHEAD TRANSFORMER PRIMARY CABLE: 2-1/0AL EPR 25kV IN EXISTING 1-4" CONDUIT WET AND DRY UTILITY CLEARANCES ·THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT TRENCH AND THE EDGE OF ANY "WET" FACILITY TRENCH IS 3' WITH THE PRESENCE OF A MINIMUM OF 1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE BARRIER. ·THE MINIMUM ALLOWABLE SEPARATION BETWEEN THE EDGE OF THE JOINT TRENCH AND THE EDGE OF ANY "DRY" NON-UTILITY FACILITY TRENCH IS 2' WITH NO LESS THAN 1' OF UNDISTURBED EARTH OR THE INSTALLATION OF A SUITABLE BARRIER. WORK REQUIREMENTS N/A N/A N/AREQUIRED TRAFFIC CONTROL PLAN / FLAGGING ENCROACHMENT PERMIT VEGETATION REMOVAL REQUIRED REQUIRED Know what's below.Call before you dig.REMOVAL 5 5 Know what's below.Call before you dig.SCALE: 1" = 5'PMI-9 DETAIL(S): LOC 1-5 SCALE: 1" = 5'SPLICE BOX: LOC 12 SCALE: 1" = 5'T730073 DETAIL: LOC 14 SCALE: 1" = 5'T128631 DETAIL: LOC 16