HomeMy WebLinkAbout1219 Monterey Inspection History with CorrectionsPERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
FOR CITY OF SAN LUIS OBISPO
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
02/14/2020 02/14/2020 Underfloor/Slab CDI-01943-2020 Partial Pass Tom Fitzgerald Yes Complete
COMMENTS ApprovedChecklist Item
Inspection Contact Info David 235-5027 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments Requesting Mark O. or Jay C.No
DWV Piping & Test X 02/14 Showroom and bathroom only. Need to test detail
shop floor drain section
Yes
Water Piping No
Gas Piping No
Electrical Conduit No
Mechanical Duct No
Floor Framing No
Underfloor Insulation No
Storm Water No
02/18/2020 02/18/2020 Underfloor/Slab CDI-02033-2020 Passed Tom Fitzgerald No Complete
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
DWV Piping & Test X 02/18 re-inspection Passed Yes
Water Piping No
Gas Piping No
Electrical Conduit No
Mechanical Duct No
Floor Framing No
Underfloor Insulation No
Storm Water No
04/27/2020 04/27/2020 Rough Inspection CDI-04416-2020 Passed Tom Fitzgerald No Complete
City of San Luis Obispo Page 1 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call No
General Inspection Comments No
Roof Nailing No
Shear Wall Nailing No
Rough Framing X (4/27)Yes
Rough Electrical X (4/27)Yes
Rough Mechanical X (4/27)Yes
Rough Plumbing/DWV test X (4/27)Yes
Rough Fire Sprinklers No
Gas Piping & Pressure Test X 04/27 Yes
Type 1 Hood - Duct Test No
Type 1 Hood - Duct Wrap 1st
Layer
No
Type 1 Hood - Duct Wrap 2nd
Layer
No
Windows No
Storm Water No
05/04/2020 05/04/2020 Surface Coverings CDI-04764-2020 Partial Pass Tom Fitzgerald Yes Complete
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments Requesting Tom No
Insulation X 05/04 approved for all except show room and sales
offices.
No
Drywall Nailing No
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling No
Fire Proofing No
Storm Water No
05/08/2020 05/08/2020 Surface Coverings CDI-04900-2020 Partial Pass Tom Fitzgerald Yes Complete
Reinspection of CDI-04764-2020
City of San Luis Obispo Page 2 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call No
General Inspection Comments No
Insulation 05/04 approved for all except show room
and sales offices.
No
Drywall Nailing X 05/08 approved for everything except service and
parts area and main service area.
No
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling No
Fire Proofing No
Storm Water No
07/22/2020 07/22/2020 Surface Coverings CDI-07210-2020 Partial Pass Tom Fitzgerald Yes Complete
Reinspection of CDI-04900-2020
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
Insulation 05/04 approved for all except show room
and sales offices.
No
Drywall Nailing 05/08 approved for everything except
service and parts area and main service area.
No
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling X 07/22 Approved for show room and sales offices only No
Fire Proofing No
Storm Water No
08/18/2020 08/18/2020 Underfloor/Slab CDI-08045-2020 Failed Tom Fitzgerald Yes Complete
Reinspection of CDI-01943-2020
City of San Luis Obispo Page 3 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
DWV Piping & Test 02/14 Showroom and bathroom only. Need
to test detail shop floor drain section
Yes
Water Piping No
Gas Piping X 08/18 Contractor no-show and gauge registered 7
pounds which did not pass the test for gas piping. Gas
piping is exposed above ground for the last 3 or 4 feet
before it ties into the building. This section of piping is to
be placed 18" underground and stubbed up in a vertical
riser at the point of connection to the building piping.
No
Electrical Conduit No
Mechanical Duct No
Floor Framing No
Underfloor Insulation No
Storm Water No
12/15/2020 12/15/2020 Final Inspection CDI-12075-2020 Failed Tom Fitzgerald Yes Complete
COMMENTS ApprovedChecklist Item
Inspection Contact Info Micheal 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
Final Plumbing No
Final Electrical No
Final Mechanical No
Fire Sprinkler Trim & Test No
Accessibility No
Stairs, Handrails & Guard Rails No
Smoke & Carbon Monoxide
Alarms
No
Electrical Meter Release X 12/14 revise electrical plans to show new panel
locations and all associated circuits breakers and loads.
No
Gas Meter Release No
Addressing No
Storm Drain Installation &
Engineering Cert
No
Storm Water No
Final Approval No
12/16/2020 12/16/2020 Final Inspection CDI-12215-2020 Passed Tom Fitzgerald No Complete
Reinspection of CDI-12075-2020
City of San Luis Obispo Page 4 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Michael 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
Final Plumbing No
Final Electrical No
Final Mechanical No
Fire Sprinkler Trim & Test No
Accessibility No
Stairs, Handrails & Guard Rails No
Smoke & Carbon Monoxide
Alarms
No
Electrical Meter Release X 12/16 approved and email sent. 12/14 revise
electrical plans to show new panel locations and all
associated circuits breakers and loads.
No
Gas Meter Release No
Addressing No
Storm Drain Installation &
Engineering Cert
No
Storm Water No
Final Approval No
07/12/2021 07/12/2021 Rough Inspection CDI-07629-2021 Failed Tom Fitzgerald Yes Complete
City of San Luis Obispo Page 5 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call No
General Inspection Comments request Tom No
Roof Nailing No
Shear Wall Nailing No
Rough Framing No
Rough Electrical X 7/12 Torro St. side. "Parts" side contractor to get permit
renewed as there's been no inspections for a year also
see correction list for necessary revisions to be
submitted for the city for electrical and mechanical and
framing.
No
Rough Mechanical No
Rough Plumbing/DWV test No
Rough Fire Sprinklers No
Gas Piping & Pressure Test No
Type 1 Hood - Duct Test No
Type 1 Hood - Duct Wrap 1st
Layer
No
Type 1 Hood - Duct Wrap 2nd
Layer
No
Windows No
Storm Water No
05/19/2022 05/19/2022 Rough Inspection CDI-05761-2022 Partial Pass Stephen Ames Yes Complete
Reinspection of CDI-07629-2021
City of San Luis Obispo Page 6 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 *REQUESTING SEAN OR BRIAN*No
Courtesy Call No
General Inspection Comments No
Roof Nailing No
Shear Wall Nailing No
Rough Framing 5.19 verified at parts/service area and office adjacent to
parts service area.
No
Rough Electrical X 05/19 Verified at parts service area and office
adjacent to parts/service area. 7/12 Torro St. side.
"Parts" side contractor to get permit renewed as there's
been no inspections for a year also see correction list for
necessary revisions to be submitted for the city for
electrical and mechanical and framing.
No
Rough Mechanical X 05/19 failed. No plans or permit for new mini splits
being installed in parts/service area. Instructed builder to
revise plans to include new systems.
No
Rough Plumbing/DWV test No
Rough Fire Sprinklers No
Gas Piping & Pressure Test No
Type 1 Hood - Duct Test No
Type 1 Hood - Duct Wrap 1st
Layer
No
Type 1 Hood - Duct Wrap 2nd
Layer
No
Windows No
Storm Water No
05/31/2022 05/31/2022 Surface Coverings CDI-06236-2022 Partial Pass Sean McCaffrey Yes Complete
Reinspection of CDI-07210-2020
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Yes, ETA in the morning No
General Inspection Comments No
Insulation X05/31 on Toro St side of bldg ok. 05/04 approved
for all except show room and sales offices.
No
Drywall Nailing 05/08 approved for everything except
service and parts area and main service area.
No
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling 07/22 Approved for show room and sales offices only No
Fire Proofing No
Storm Water No
City of San Luis Obispo Page 7 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
06/07/2022 06/07/2022 Surface Coverings CDI-06248-2022 Partial Pass Sean McCaffrey Yes Complete
Reinspection of CDI-06236-2022
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080 No
Courtesy Call Please call No
General Inspection Comments Requesting Sean No
Insulation 05/31 on Toro St side of bldg ok. Remaining okay
05/04 approved for all except show room and sales
offices.
Yes
Drywall Nailing 6/7 Okay and finished 05/08 approved for
everything except service and parts area and main
service area.
Yes
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling 07/22 Approved for show room and sales offices only No
Fire Proofing No
Storm Water No
06/28/2022 06/28/2022 Surface Coverings CDI-07115-2022 Partial Pass Stephen Ames Yes Complete
Reinspection of CDI-06248-2022
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 748-8080/748-8083 No
Courtesy Call Yes No
General Inspection Comments No
Insulation 05/31 on Toro St side of bldg ok. Remaining okay
05/04 approved for all except show room and sales
offices.
Yes
Drywall Nailing 6/7 Okay and finished 05/08 approved for
everything except service and parts area and main
service area.
Yes
Gas Pressure Test No
Shower Pan No
Exterior Lath & Flashing No
T-Bar/Suspended Ceiling X6/28 Verified all except strapping at lights. Need to
verify. Also need to verify bonding at ceiling metal boxes.
07/22 Approved for show room and sales offices only
No
Fire Proofing No
Storm Water No
09/14/2022 09/14/2022 Site Work CDI-10128-2022 Partial Pass Sean McCaffrey Yes Complete
City of San Luis Obispo Page 8 of 9June 23, 2025
PERMIT INSPECTION HISTORY REPORT (BLDG-1668-2018)
Building 08/15/2018Application Date:Permit Type:Owner:GARRIS BRIAN D FAMILY TRUST (TR
1)
ParcelAlt/Addition - Commercial 06/26/2019Work Class:Issue Date:002-331-001
Issued 03/14/2023Expiration Date:Status:Address:1219 Monterey St
San Luis Obispo, CA 93401
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection
Required?CompleteActual
Start Date
COMMENTS ApprovedChecklist Item
Inspection Contact Info Mike 805-748-8080 No
Courtesy Call No
General Inspection Comments X 9/14 exterior concrete pour. Okay; sidewalk to private
path of travel will be look at as blended transitions. Will
need to float in front of new double doors to be less than
2% slope. Okay to pour
No
Sewer Lateral No
Water Service No
Gas Piping & Pressure Test No
Electrical Conduit No
Storm Drain No
Temporary Power Pole No
Site Visit/Pre-Con Meeting No
Storm Water No