HomeMy WebLinkAbout60 Casa Inspection Report 10.08.24Occupant:SAGRADO CORAZON
TOWNHOMES
Occupant Name:SAGRADO CORAZON TOWNHOMES
Street Number:60 Occupant Code:880
Street Name:Casa City:San Luis Obispo
Street Type:Street Postal Code:93405
Inspector:Diepenbrock, Arlen State:California
First Name REG
Property
Manageme
nt
Email info@regmgmt.com
Work Phone 805-541-6664
09/25/2025 17:06
Complete Inspection Report - With Documents
Facility Information
Contact
Inspection Information
Inspection Type:Annual
Page 1 of 3
Occupant:SAGRADO CORAZON
TOWNHOMES
09/25/2025 17:06
Violations
Violation
Code Description
906.1 Where required.
Portable fire extinguishers shall be installed in all of the following locations:
1.In new and existing Group A, B, E, F, H, I, L, M, R-1, R-2, R-2.1, R-2.2, R-3.1, R-4 and S occupancies.
Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C.
2.Within 30 feet (9144 mm) distance of travel from commercial cooking equipment and from domestic
cooking equipment in Group R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored, used or dispensed.
4.On each floor of structures under construction, except Group R-3 occupancies, in accordance with
Section 3316.1.
5.Where required by the sections indicated in Table 906.1.
6.Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
7.Large and small family day-care homes shall be equipped with a portable fire extinguisher having a
minimum 2-A:10-B:C rating.
8.Where required by California Code of Regulations, Title 19, Division 1.
9.Within 30 feet (9144 mm) of domestic cooking equipment located in a Group I-2.
[California Code of Regulations, Title 19, Division 1, §3.29(a) through (d)] Portable Fire Extinguishing
Equipment.
(a)General. Portable fire extinguishers conforming to the requirements of California Code of
Regulations, Title 19, Division 1, Chapter 3, shall be installed and maintained in accordance with guides
established therein.
(b)Special Coverage. Additional Class A, B and C units of adequate extinguishing potential shall be
provided for any other hazard, as determined by the enforcing agency.
(c)Group A Occupancies.
(1)One additional Class 2-A unit shall be provided in Group A Occupancies as follows:
(A)On each side of the stage or platform.
Exception: Platforms 1000 square feet or less in area need have only one such extinguishing unit.
(B)On each side of every fly gallery.
(C)In basements beneath the stage or platform.
(D)In every hallway or passageway leading to a dressing room.
(E)In every property room, carpenter shop or similar workroom.
(2)Not less than one 10-B:C unit (not less than 4-B:C for existing extinguishers in existing occupancies)
shall be provided:
(A)For each motor and fan room.
(B)Adjacent to each switchboard on the stage or platform.
(C)For each motion picture machine in projection rooms.
Exception: One 20-B:C unit (not less than 8-B:C for existing extinguishers in existing occupancies) in
each projection room may be accepted as providing substantially equal protection.
(3)The enforcing agency may allow modifications or deviations relative to the number and location of
portable fire extinguishers as required by this section provided such authority finds that the basic intent
of this section and the ease of accessibility to extinguishers is otherwise achieved.
(d)Group R-2.1, R-3.1 and R-4 Occupancies. In Group R-2.1, R-3.1 and R-4 occupancies, a continuously
attached garden hose, equipped with a water flow control nozzle, may be provided in lieu of one or
more required fire extinguishers when acceptable to the enforcing agency. The location and length of
such hose shall be as designated or approved by the enforcing agency.
NOTE: It is recommended that, wherever possible, portable fire extinguishers be located adjacent to
manual fire alarm sending stations.
[California Code of Regulations, Title 19, Division 1, §565(a)] Selection of Fire Extinguishers.
(a)The selection of extinguishers for a given situation shall be determined by the authority having
jurisdiction in accordance with adopted codes or ordinances. The character of the fires anticipated, the
construction and occupancy of the individual property, the vehicle or hazard to be protected, ambient-
temperature conditions and other factors shall be considered. The number, size, placement and
limitations of use of extinguishers required shall be determined by using California Code of Regulations,
Title 19, Division 1, Sections 567 through 573.
Exception: Portable fire extinguishers are not required at normally unmanned Group U occupancy
buildings or structures where a portable fire extinguisher suitable to the hazard of the location is
provided on the vehicle of visiting personnel.
Page 2 of 3
Occupant:SAGRADO CORAZON
TOWNHOMES
2 Inspection Fee:0.00
09/25/2025 17:06
Violation
Code Description
907.6.5 Access.
Access shall be provided to each fire alarm device and notification appliance for periodic inspection,
maintenance and testing.
Inspection Notes
Property is well kept. Please continue to regularly check CO detectors, smoke alarms and dryer vents in each unit.
Please address the fire extinguishers & fire alarm room key.
Please contact fire department for reinspection. If you have any questions about violations or reinspection please
coordinate with Inspector Arlen Diepenbrock at adiepenb@slocity.org or 805 503 2062.
Documents
Inspection Documents
Violation Documents
Page 3 of 3