HomeMy WebLinkAboutTank Testing 2C C T T Central Coast Tank Testing Post Orrice Box 2155. Santa Barbara. CA 93120 May 26, 1990 Mr. Scott Kenyon Southern Pacific Milling Co. 3555 Vineyard Avenue Oxnard, CA 93030 Subject: UNDERGROUND FUEL STORAGE PRECISION TANK TESTS SAN LUIS OBISPO COUNTY LOCATIONS Dear Sir : The purpose of this report is to transmit the results from Central Coast Tank Testing's precision tests of the underground storage tanks at your facilities located in Santa Margarita and San Luis Obispo, California concluded on Saturday, May 26, 1990. BACKGROUND The system used to perform the test is the Horner "Ezy-Chek" Tank Testing System. This system meets or exceeds the NFPA x*329-87 guidelines. These guidelines are the basis of all mandated requirements at the state, county or local agency levels. The system is capable of detecting a product volume variance rate of 0.05 gallons per hour. The product volume variance rate is an equipment tolerance, rather than a permissible leak rate. Central Coast Tank Testing assumes no responsibility for product leakage. Our responsibility extends only to testing of tanks as tight or not tight, as of the date tested, according to state compliance guidelines, and within the accuracy tolerance of the Horner Testing System. Testing methodology is also included that meets the statistical review of the data collected. Groundwater was not considered for the testing. The variables in testing; such as tank end deformation, entrapped vapor, evaporation, and temperature, are noted on the individual data sheets, if encountered. Testing and preparation comments are also noted. RESULTS Santa Margarita Location Tank 1-10,000 gallon diesel system. This system test was performed over a period of two hours and tested tight in compliance. The hydrostatic pressure applied to the system was adequate. The volume change, corrected for the influence of temperature, produces an improving product volume variance rate of -0.03 to -0.013 yellows per hour. AaNilionally, the 95X cnn/ia(!?nce intervals oroditcwd were within the ne» criteria limits Tank 2-20,000 gallon diesel system. This system test was performed over a period of two hours and tested tight in campli.&=e The hydrostatic pressure applied to the system was adequate. The volume change, corrected for the influence of temperature, produces an improving product volume variance rate of 0.00 to *0.0.T0 ywllons per hour. Adflilionally, the 95Ar cvnfiddncw intervals pradacwd were within the 78* cite.-ia limits San Luis Obispo Location Tank 3 - 10,000 gallon diesel system. This system test was performed over a period of two hours and tested light in compliances The hydrostatic pressure applied to the system was adequate. The volume change, corrected for the influence of temperature, produces an improving product volume variance rate of -0.02 to -0.027 gwllons per hoai: Additionally, the 95S cVnfiaLoncw intervals 0r0ducVd were within the new c.-iMris limits Respectfully submitted, �Avkoll� Robert P. Hankenson Central Coast Tank Testing 2 ,UNDERGROUND TANK TESTS .�;, INC. Horner 917 W. Belleview TANK CERTIFICA. i ION & EZY CHEK- Porterville, Ca 93257 LOCATION DATA CHART leak detector Phone (209) 781-6508 NOTICE: It is the owner's responsibility to contact the environmental health department of any failures within 24 Hours of the results given to the owner. OWNER'S Property NAME / !L](Z A VG Na a Telephone Tank(s) I{d' J p L r Address City Zip County J NAME OF LOCATION I t r A[ L c Name Address Telephone REASON FOR TEST 1,6 M/ (Explain Fully) WHO REQUESTED TEST AND WHEN NameP Title Date U C fA S .4 n/ ( —if ell0 Address Telephone 2 <L -- y -8 u WHO IS PAYING FOR THIS TEST? ny, Agency Individual Tete 1e u L Ming Address City Isle Zip ITEM OR SYSTEM TESTED Identify by Direction of owner IDq Capacity Brand/Supplier Grade Approx Age Steel Fiberglass / TANK ONLY U O l e e L 1,,Ajbk4 Al❑ ❑ c PRODUCT LINE VENT LINE ❑ ❑ VAPOR LINE ❑ ALL OF THE ABOVE ❑ El 0 ❑ ❑ INSTALLATION DATA Location h So4Tu /off 5 h m� �• �g • North inside driveway, Rear of station,etc. Cover Concrete ❑ Blacktop ❑ Earth Other Fills 4„ 3" [A,--'-0 El 2" ❑ 1t/i" ❑ Other Size Remote Fills ❑ Vents U Size Mamfolded Yes ❑ No �� Siphones Yes C No f�I Which tanks? Pumps Suction Bo Hand ❑ e ❑ HYDROSTATIC TEST ON LINE ❑Yes Gl11rf Vapor LN.ne 1 ❑ Stage 2 ❑ UNDERGROUND WATER Is the water overthelank? El Yes r � Ifur Depth to the Water table ANo A.-J, At y �7 Tanks to be filled / is 0 0hr J O• o Dale Distributor �• !. � . D-e L,.j A a FILL -UP ARRANGEMENTS Extra product to "top off" YES NO Name rbs S 0j X� Telephone CONTRACTOR, any other MECHANICS, contractor involved OTHER INFORMATION OR REMARKS Additional information on any items above Officials or others to be advised when testing is in progress or completed Visitors or observers present during test etc Tests were made on the above tank systems in accordance with Horner EZY Check Leak Detection test TEST RESULT procedures prescribed for as detailed on attached test charts with results as follows: Tank Identification It Lines Only Tight Leakeage Indicated Date Tested TANKS f Yes No El — _ PRODUCT LINES Po/ Yes ❑ No ❑ Yes ❑ No ❑ Ve w& Vent Yes 300"- Yes ❑ No ❑ Lines Included No ❑ Yes ❑ No ❑ CERTIFICATION .2-10-K? Dale This is to certify that these tank systems were tested on the date(s) shown. Those indicated as "Tight" meet the criteria established by the (National Fire Protection Association Pamphlet 329.) CALIFORNIA UNDERGROUND STORAGE TANK REGULATIONS ARTICLE 4 SECTION 2643 ( ) N )O DENNIS E GOODAN Technician UNDERGROUND TANK TESTERS, INC./By: Signature �.mim Ift"N 1,11.211. 1WHITE — FILE CANARY — County PINK — Horner G.R. — Customer L0 N r I\ �f O (� � z z �r O w F- p� o m r. J a U ir ❑ (� = U o z z z C7 w m L 0 U w w cr fn fn a m Cr W L( o O � ~ U w ao LLJ (� ❑ a d F- LU C N (n o O� U (Da ILE I I a w � Z O J 2 U o.. 11 w N U) `1 z 90 F- U O cr d J w w J U) LU W 0 z Y z H H z w U LL LL w O U a w U O ♦- > a C7 w cr D In w 9 iLL O` H E u) w LL 02 LL O u � u ❑ LL } 0( 2 a H > rl W z O ❑ z N LU W Q o ) w ❑ frr cr W a a > cn z O F U U W H r w z LL O omC W a F- I}- ❑ Y � Z LU Q � H a z "- W Q U OM LL, LC rj - c CA r� c v r J J z0 LLw \ �. LC C� oc w� C Ir LU — n l it l u l n l u 1 11 n 1 II 1 (1 1 it I v v cc V� mm x x T x x x^ x x x X x x x + ` z In aCO �° I , I e 1 c 1 I �• �1 I �` II II p 11 11 11 n It 11 II z w w �` C al I I I I I I I� I I I z uj Q Q �- HU) J w ww _ v J� II C II ( 1 II ( 11 II I II I II`I• II II I 11 Q Q x x 1 LX x x x x x x x x x x + zCQ �o I I I 1 I 1 11 II II II II II I 11 I II 1 II It W o > z W w J ' I\�V`\ I 1 1 I J F- LU W I I I I I I I I I I i Jln Ol N c Y Ir Q W cc UNDERGROUND TANK TESTERS, INC. 917 W. Belleriew Potterville, CA 93257 c GFF"Eh1T u dal aI _( D A80VF- ") e I GigcumoTANK I KA 5f- R �A0b q-- GRAVEL IfO, o Sf� ;�. ;► ob' G �• R v E I Id A Y 80 ~170 -50 .40 30 -20 - a � �(\ � / � ��j� •! it <> - CN V v � / '1 UNDERGROUND TANK TESTE►..s, INC. Horner 917 W. Belleview TANK CERTIFICA�t ION & �iY �M' Porterville, Ca 93257 LOCATION DATA CHART leak detector Phone (209) 781-6508 NOTICE: It is the owner's responsibility to contact the environmental health department of any failures within 24 Hours of the results given to the owner. OWNER'S Property NAME Tank(s) r Co. S- 0 �v' O amb IF Telephone t VS b. Address e City Zip County NAME OF LOCATION .I 69Atj,(- Ala. V Ckm�,yb -SAArA 6jeqAum Name Addross Telephone REASON FOR TEST (Explain Fully)SRAJ WHO REQUESTED TEST AND WHEN p I Z I o Na Title Dale V t c4.3A AILD 14 O C Address feiepnone WHO IS PAYING FOR THIS TEST? c.L I -XTO0 oygpany, AgeIndividual Telephone �' n or S u C C A siq v r, N C6. L Billing Address city State Zip ITEM OR SYSTEM TESTED Identify by Direction of owner IDfI Capacity Brand/Supplier Grade Approx Age Steel Fiberglass TANK ONLY m/ l DO u N KNo c sc L U AJrow ❑ PRODUCT LINE %.-I ❑ ❑ VENT LINE ❑ ❑ VAPOR LINE ❑ ALL OF THE ABOVE ❑ ❑ ❑ INSTALLATION DATA Location U/JiI C K o, �LJ North inside driveway, Rear of station, etc. Cover / Concrete fa/ Blacktop a ' Earth 4/ Other Fills 4" ElF / 2" ❑ 11/2" Luce Other Size Remote Fills ❑ Vents /) if p(Size Mandotded Yes ❑ No m/ Srphones Yes E1 No Cam' Which tanks? Pumps Suction �Y Hand ❑ Turbine ElS HYDROSTATIC TEST ON LINE ❑T Yes Yi.M' Vapor Recovery None Stage 1 ❑ Stage 2 ❑ UNDERGROUND WATER Is the water over the tanks El Yes Depth to the Water table U A2jC +/ 0" N FILL -UP ARRANGEMENTS p Tanks to be filled 1 YOu hr 2 to Distributor Name , Extra product to "top off' YES NO Telephone CONTRACTOR, any other MECHANICS, contractor involved A Rt�IC Lrat. ,j ws Coutit OTHER INFORMATION OR REMARKS Additional information on any items above. Officials or others to be advised when testing is in progress or completed. Visitors or observers present during test etc. Tests were made on the above tank systems in accordance with Horner EZY Check Leak Detection test TEST RESULT procedures prescribed for as detailed on attached lest charts with results as follows: Tank Identification # Lines Only Tight Leakeage Indicated Date Tested Yes pl No ❑ f.J TANKS PRODUCT LINES 4d, Yes ❑ No ❑ Vaftm & Vent Yes Wool"' Yes ❑ No ❑ Lines Included No ❑ Yes ❑ No ❑ Yes ❑ No ❑ CERTIFICATION This is to certify that these tank systems were tested on the date(s) shown. Those indicated as "Tight" meet the criteria established by the (National Fire Protection Association Pamphlet 329.) CALIFORNIA UNDERGROUND STORAGE TANK REGULATIONS ^ ARTICLE 4 SECTION 2643 ( ) J / I DENNIS E. GOODAN e1. e /, t,�. ` , Technician UNDERGROUND TARKTESTERS. INC./By: Signature SEQUOIA PRINTING - VISALIA 73431 ]B ' WHITE — FILE CANARY — County PINK — Horner G.R. — Customer cn r I S ✓ �m � Ir I I I I I I I I I I h 1, m m J Z O m 11 11 11 ' 11 I� ' II f II 1 It II II r0 O x x x x x x x x x x v � � II 11 II II II 111 II 11 II II e` Y mr mm cm rr 1 -C -C 47— 1" D m DO I I I I I I N I — I N I I II II r"NN II 11 II II 11 .N II II Z I � � I 111 I I I r0 O D � Z V _x x x x x x x x x x Jv ♦ \ �V x x .s O7 m J.J J J m m � m v � II II U �' II I II � 11 II II U I II mT CO C D r m D D D m m c ) 2 m o Z ° D El Z (1) m r m < m r ❑ O c m n :0 O 0o m m -< K m �� 0 o c ° O a c � n z 0 m m m n m z D O O D m Jo Z 1 D ❑ n m cn D< G) N ❑ Z O Z m m D r C ❑ 2 Z W Z N 4 m m c� `O D D Z Z C n D Z -nzr O x m0' m oZ m � o D n n Z m z z --I •I 2 Km 2 < ITT C 2° X - D � O °O C (n F m r O Z G) 70 D m m m m m /1 � O O T D :0 --1 1, -0 II ❑ G) m z n m v 1 z M6- OZ m Z❑ M �p D m Z v m =0�C O O -4 z m�§o m oxco � D 1 m m Z o� n xm cc, m m V co G Z Z O N C." 2 D ❑ 2 D r o O z Z A-� y� z o cn 0 �p lo , Ic,J Parnp 000 (At -,r _ _ r� UNDERGROUND TANK TESTERS, INC. 917 W. Belleview Portervilk CA 93257 OFF ►CF 1;-W SA AD ¢ C--MEN- Co 14 br-lim),60 ga). - SA 14TA rri .? ,ZGAR i T A rfk ,