HomeMy WebLinkAboutSolar App Approval Documents
Inspection Checklist
Address:
168 Earthwood Ln
San Luis Obispo, CA 93401
Approval ID:
SA20230823-2142-233-1576-A
AHJ:
City of San Luis Obispo, CA
Scope of work:
INSTALLATION OF ROOF
MOUNTED PV SYSTEM - 4.46KW
(11 PANELS) - LOT 62
General Guidelines
The installer shall follow the manufacturer's instructions for all installed equipment and shall have them available at
the time of inspection.
All wire sizes shown are a minimum, unless indicated otherwise, and the installer may upsize them at their
discretion.
All OCPD ratings shown must match the inspection checklist and be installed per the equipment manufacturer's
instructions, any ratings that do not match the inspection checklist are valid reasons for inspection failure.
Conduit sizing to be confirmed at time of inspection. Contractor to provide conduit fill calculations where requested
by inspector
Where distribution equipment, such as the main service panel or subpanel buses, are fed simultaneously by a
primary source(s) of electricity and one or more other power sources, interconnection shall have a method of
compliance at each panel board with both a primary source and other power source(s).
Main Service Panel Equipment Pass
If grounding electrode is rod, pipe or plate, then supplemental electrode is properly installed. Exception: If a
single rod, pipe, or plate grounding electrode has a resistance to earth of 25 ohms or less, the supplemental
electrode shall not be required.
EGC is installed ensuring continuity to all system components and finally to grounding electrode.
Single Phase Grid Voltage 240 V
Busbar 1 Pass
Existing Main Service Panel
Generation sources are connected directly to the Existing Main Service Panel
Existing Main Service Panel busbar ampere rating 225 A
Rating of the OCPD protecting the Existing Main Service Panel 200 A
Backfeed breakers are at opposite load ends of the panel.
For center fed panels, backfeed breakers are on one side of main breaker and not both in the panel.
Busbar 2 Pass
PV Combiner Panel
PV Combiner Panel busbar ampere rating 100 A
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 1/30
NEC 2020 PV (rev_k)
The length of the section of the PV Combiner Panel feeders that is inside a raceway is less than or equal to
2 feet
Conductor gauge for the PV Combiner Panel feeders 10
Raceway size for the PV Combiner Panel feeders is compliant with 300.17 and
Chapter 9 Yes
Busbar 2 Pass
Equipment: Point of Connection Pass
Utility Service Rating 225 A
Equipment Point of Interconnection Pass
All power production inverter outputs have the same point of connection.
Connected equipment is within line of sight and closer than 10ft to the point of interconnection or a
disconnect/isolation means are installed.
There is no existing Utility interactive power production source connected to the home’s electric service. -
Only the utility interactive power production sources and/or photovoltaic modules specified on this
inspection checklist list are present on site.
DC and AC conductors are copper, Class B or Class C, and THWN-2, NM or PV Wire, or they are a
jacketed multiconductor cable assembly listed and identified for the application.
All power terminals are rated to 75°C or greater, labeled for use with Copper Class B or Class C wires, and
accept at least 8 AWG wire.
Conductors are properly terminated and wired according to the code.
Where Equipment Grounding Conductors (EGC) or Grounding Electrode Conductors (GEC) are not routed
with circuit conductors, they are a minimum of 6 AWG or they are protected from physical damage
There is a minimum working clearance according to the code; for all components that may require service,
the standing area of the workspace shall not contain obstructions, abrupt changes in grade, or irregularities.
Installed equipment and OCPDs are either rated to 22kAic or listed series rated or protected by sufficient
wire length to reduce the AFC to less than 10kA
Inverter Pass
Inverter architecture:Microinverters
EGC Wire Size Inverter 1 12 AWG
Overcurrent Protective Device rating for each branch circuit of microinverters or
AC Module 20 AMP
AC Wire size Inverter 1 12 AWG
Maximum number of THWN-2 conductors in a PV inverter AC output circuit
raceway, excluding any equipment grounding conductors.2
Inverter 1 model number IQ7HS-66-M-US [240V]
Inverter 1 manufacturer Enphase Energy Inc.
Quantity of modules accepted by the microinverter 1
AC NM Wire size Inverter 1 12 AWG
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 2/30
NEC 2020 PV (rev_k)
PV inverter maximum input DC open circuit voltage (Voc) on the equipment label 59 V
PV inverter maximum input DC short circuit current (Isc) on the equipment label 15 A
Presence of Rapid Shutdown switch label per Fire Bulletin
NM cable is installed for inverter output circuits in locations and uses according to the Code.
Inverter Pass
Roof and PV Array Pass
The system will be installed on a permitted structure
Racking System Model Number InvisiMount
Racking System Manufacturer SunPower
The module and racking system shall be installed per the racking manufacturer's
installation instructions regarding grounding and bonding, fire, and load ratings Yes
Attachment points of the mounting system are staggered Yes
Maximum spacing in inches between adjacent attachment points of the mounting
system 48"
Roof penetration sealant method has been installed per the manufacturers instructions.
The distance from the lowest point of the module to the roof surface does not
exceed 4 in
The roof structure appears to be structurally sound, without signs of alterations or significant structural
deterioration or sagging.
Quantity and spacing of structural attachments match the installation instructions per manufacturer.
Array conductors are secured and supported. Installed so as not to damage the cable, at intervals not
exceeding 1.4 m (4.5 ft) and within 300 mm (12 in.) of every cable entry into enclosures such as outlet
boxes, junction boxes, cabinets, or fittings.
PV Module model number Q.PEAK DUO BLK ML-
G10+ 405
PV Module manufacturer Hanwha Q CELLS
PV Module quantity 11
MLPE equipment listed as PVRSS or PVRSE installed on each module.Yes
All rooftop conduits are mounted at least 7/8” above the roof surface.
All conductors installed without raceway are listed as PV Wire, USE-2 or Type distributed generation (DG)
cable
Roof Plane 1 Pass
Pitch 5/12
Roof Covering Asphalt or composition
shingles
Number of coverings of comp shingle 1
Fire Pass
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 3/30
NEC 2020 PV (rev_k)
The home has sprinklers.Yes
Percentage of the Roof with a Solar Array 19.65%
Fire Pathways, venting and access in accordance with the SolarAPP Fire Bulletin and/or the AHJ
requirements therein
Disconnecting Means are in compliance with the SolarAPP Fire Bulletin
Signage, Placards, Directories and Markings in accordance with the SolarAPP Fire Bulletin
The installation is in compliance with the AHJ Fire Bulletin Appendix Confirmed
Maximum AC operating current in labels 17.6 A
Maximum AC operating voltage in labels 240 V
Fire Pass
Corrections
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 4/30
NEC 2020 PV (rev_k)
SolarAPP+ Fire Bulletin
Disconnecting Means SolarAPP+ Fire Bulletin
PV System
PV system disconnecting means shall be provided in accordance with the 2020 National Electrical Code® (NEC), NFPA 70.(R) [690.13]
A Rapid Shutdown switch shall be provided at a readily accessible location outside the building in accordance with the 2020 National
Electrical Code® (NEC), NFPA 70.® [690.12(C)]
Signs, Placards, Directories, and Markings
Guidance
SolarAPP+ Fire Bulletin
General
All labeling shall comply with Section 324 of the 2021 International Residential Code and Articles 690 and 705 of the 2020 National
Electrical Code® (NEC), NFPA 70
All labeling shall comply with [NEC 110.21 (B)]
Rapid Shutdown Label
Buildings with more than one rapid shutdown type:
A detailed plan view diagram showing each PV system and a dotted line around areas that remain energized after the rapid shutdown
switch is operated. [NEC 690.56(C)]
Rapid Shutdown (PV Hazard Control) switch:
This switch shall have a label not greater than 3 feet from the switch that states the following:
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM [NEC 690.56(C)(1)]
Roof Access, Egress, and Ventilation SolarAPP+ Fire Bulletin
General
Access and minimum spacing shall be provided for access to specific areas of the roof, emergency egress from the roof and opportunities
for smoke ventilation in accordance with the 2021 International Residential Code [IRC 324.6]
References:
Ridge Setbacks - [IRC R324.6.2]
Sprinklered Occupancies - [IRC R324.6.2.1]
Pathways - [IRC 324.6.1]
Emergency escape and rescue openings - [IRC R324.6.3]
Exceptions:
Detached, non-inhabitable structures [IRC R324.6 Ex. 1]
Low-slope roofs with pitch of less than or equal to 2:12; this exception may not be valid depending on the jurisdiction. [IRC R324.6 Ex. 3]
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 5/30
NEC 2020 PV (rev_k)
BIPV systems listed and labeled in accordance with Section 690.12(B)(2) of NFPA 70, where the removal or cutting away of portions of the
BIPV system during fire-fighting operations has been determined to not expose a fire fighter to electrical shock hazards. [IRC R324.6 Ex. 4]
Carbon Monoxide, Smoke & Heat Detectors SolarAPP+ Fire Bulletin
Guidance:
Where required, Carbon Monoxide and smoke detectors shall be provided in accordance with the code or an Affidavit has been provided
by the customer. 2021 International Residential Code. [R314, R315]
Fire Classification SolarAPP+ Fire Bulletin
PV System
Rooftop-mounted PV systems shall have the same fire classification as the roof assembly required in 2021 International Residential Code.
[R902.4; R324.4.2]
Building-integrated photovoltaic products installed as the roof covering shall be tested, listed, and labeled for fire classification. [IRC
R902.3, R324.5.2]
Building-integrated photovoltaic products installed as the roof covering shall comply with the minimum requirements for fire classification
set by the jurisdiction. [IRC R902.1]
Product Certifications SolarAPP+ Fire Bulletin
PV System
PV panels and modules shall be listed and labeled to UL 1703 and/or both UL 61730-1 and UL 61730-2 [NEC 690.4(B)][IRC R324.3.1]
Inverters shall be listed and labeled to UL 1741 [NEC 690.4(B)][IRC R324.3.1]
Hazard Control System
Hazard control system shall be listed and labeled to UL 3741 [NEC 90.7; 110.3(C); 690.4(B); 690.12(B)(2)(1); 690.12(D)]
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 6/30
NEC 2020 PV (rev_k)
Signs, Placards, Directories, and Markings SolarAPP+ Fire Bulletin
Service Disconnect
SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY.
Simple Diagram Here
Location: At each service equipment location to which the PV
systems are connected.
Code: [NEC 690.56(C)]
RSD Initiation Device
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
Location: Rapid shutdown initiation device.
Code: [NEC 690.56(C)(2)]
Point of Interconnection
CAUTION: MULTIPLE SOURCES OF POWER
(LAYOUT OR DESCRIPTION)
Location: Service location or approved readily accessible location
Code: [NEC 705.10]
WARNING:
DUAL POWER SOURCE
SECOND SOURCE IS PV SYSTEM
Location: Electrical Equipment containing overcurrent devices in
circuits supplying power to a busbar or conductor supplied from
multiple sources
Code: [NEC 705.12 (C)]
WARNING:
POWER SOURCE OUTPUT CONNECTION -
DO NOT RELOCATE THIS OVERCURRENT DEVICE
WARNING:
THIS EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL
RATING OF ALL OVERCURRENT DEVICES EXCLUDING MAIN
SUPPLY OVERCURRENT DEVICE, SHALL NOT EXCEED
AMPACITY OF BUSBAR
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 7/30
NEC 2020 PV (rev_k)
Location: At back-feed breaker if using 120% rule (if applicable)
Code: [NEC 705.12(B)(3)(2)]
Location: At distribution equipment adjacent to the back-fed
breaker from the power source when using this "sum of breakers"
code compliance rule.
Code: [NEC 705.12(B)(3)(3)]
PHOTOVOLTAIC POINT OF INTERCONNECTION
MAXIMUM AC OPERATING CURRENT:
MAXIMUM AC OPERATING VOLTAGE:
Location: All interactive system(s) points of interconnection.
Code: [NEC 690.54]
DC Circuit Raceways and Enclosures
PHOTOVOLTAIC POWER SOURCE
Location: Unless located and arranged so the purpose is evident,
labels will be required for DC Circuit Raceways and Enclosures,
conduit, and combiner/junction boxes.
Code: [NEC 690.31(D)(2)]
PV System Disconnect
WARNING:
ELECTRIC SHOCK HAZARD TERMINALS ON LINE AND LOAD
SIDES MAY BE ENERGIZED IN THE OPEN POSITION
Location: DC Disconnecting Means where terminals on both line
and load side may remain energized. Example language or
equivalent.
Code: [NEC 690.13(B)]
PV SYSTEM DISCONNECT
Location: Each PV System Disconnect (May be AC or DC)
Code: [NEC 690.13(B)]
DC String Inverters Equipment Disconnects
PHOTOVOLTAIC DC DISCONNECT
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 8/30
NEC 2020 PV (rev_k)
WARNING:
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD
SIDES MAY BE
ENERGIZED IN THE OPEN POSITION
Location: Each PV system disconnecting means where line and
load may be energized in the open position
Code: [NEC 690.13(B)]
Location: Each PV system disconnecting means.
Code: [NEC 690.13(B)]
PV SYSTEM MAXIMUM VOLTAGE:
Location: At each DC PV system disconnecting means.
Code: [NEC 690.53]
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 9/30
NEC 2020 PV (rev_k)
FIRE SAFETY CODE REQUIREMENTS
Does the home have sprinkler systems?Yes
Percentage of Roof Area covered with PV
Total Array Area / Total Roof Area
19.65%
Roof Access and Ventilation Diagrams
Fire Safety
Ridge Setbacks
PV Less Than 33% Roof Area (66% for homes with sprinkler
systems) or per AHJ appendix.
Emergency Escape & Rescue Opening
Minimum 3’ Emergency Escape Pathway
Hips and Valley Setbacks
PV Less Than 33% Roof Area - Street Access (66% for homes with
sprinkler systems) or per AHJ appendix.
PV Less Than 33% Roof Area - Driveway Access (66% for homes
with sprinkler systems) or per AHJ appendix.
Powered by TCPDF (www.tcpdf.org)
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 10/30
NEC 2020 PV (rev_k)
Intentionally Blank
Uploaded Datasheet - 2142-fire-bulletin-appendix.pdf
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 11/30
NEC 2020 PV (rev_k)
INPUTS
Permit Details [80.19(H) ; R105.3]
GENERAL
Project Information
Project Title Avila Ranch - Lot 62 - 168
Earthwood Lane
Address 168 Earthwood Ln San Luis
Obispo, CA 93401
Homeowner's full name WCP DEVELOPERS, LLC
(WATHEN-CASTANOS)
Confirm that you have verified the homeowner's information and right to install on
the property.
Confirmed
AHJ City of San Luis Obispo, CA
Project Type PV
Code Cycle 2020/2021
Scope of Work INSTALLATION OF ROOF
MOUNTED PV SYSTEM -
4.46KW (11 PANELS) - LOT 62
PV System Size AC (kW)4.224
PV System Size DC (kW)4.455 kW
General
Confirm you have reviewed SolarAPP eligibility:Yes
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 12/30
NEC 2020 PV (rev_k)
General
The system will be installed on a permitted structure 1
Inspection Guidelines
Where distribution equipment, such as the main service panel or subpanel buses, are fed simultaneously by a primary
source(s) of electricity and one or more other power sources, interconnection shall have a method of compliance at each
panel board with both a primary source and other power source(s).
Contractor Information
Installation Applicability and Compliance
All work will comply with the 2020 National Electrical Code (NFPA 70), the International Code Council 2021 I-Codes,
Minimum Design Loads and Associated Criteria for Buildings and Other Structures (ASCE/SEI7-16), UL Standards,
Manufacturer's instructions, and Municipal requirements.
State License
Type state
Number 890895
City Business License
Type city
Number 111365
Inspection Guidelines
The installer shall follow the manufacturer's instructions for all installed equipment and shall have them available at the
time of inspection.
All wire sizes shown are a minimum, unless indicated otherwise, and the installer may upsize them at their discretion.
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 13/30
NEC 2020 PV (rev_k)
All OCPD ratings shown must match the inspection checklist and be installed per the equipment manufacturer's
instructions, any ratings that do not match the inspection checklist are valid reasons for inspection failure.
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 14/30
NEC 2020 PV (rev_k)
FIRE
I hereby affirm that I will comply with all requirements and guidelines as set out by
the SolarAPP Fire Bulletin.
Confirmed
I hereby affirm that I will comply with all requirements and guidelines as set out by
the AHJ Fire Bulletin Appendix
Confirmed
Does the home have sprinkler systems?Yes
What is the total array area?227.34 sqft
Total roof area 1157 sqft
Percentage of Roof Area covered with PV
Total Array Area / Total Roof Area
19.65%
See Fire Setback Diagram attached.Less Than 33/66
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 15/30
NEC 2020 PV (rev_k)
STRUCTURAL DETAILS
General
The weight of the PV system in lbs/sq ft [IRC R301.4]2.4 psf
The ground snow load is [IRC Table R301.2] [IRC Fig R301.2(3) R301.2(4)]0 lb/sqft
Proposed maximum spacing in inches between adjacent attachment points of the
mounting system
48"
Will attachment points of the mounting system be staggered?Yes
The number of roof surfaces at different slopes and/or orientations that will be used
for installation are:
Note: 1 means all roofs used have the same orientation.
1
Type of mounting for the PV system Flush mount
Mounting Planes
Mounting Plane Type 1
Maximum distance from the lowest point of the module to the roof 4"
The current roof covering is [IRC Section R905]Asphalt or composition shingles
The number of comp shingle layers that are currently present is 1
The pitch of the roof surface is [IRC Section R905]5/12
Wind Speed
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 16/30
NEC 2020 PV (rev_k)
Is the solar module and mounting system rated by the manufacturer to withstand the
upward force of the local wind speed (110 MPH) and evenly distribute load into the
supporting structure at the proposed maximum spacing, and confirmed in UL 1703
or 61730 (Part 1 & 2), and 2703 listings? [IRC R324.4.1.2; R324.3.1]
Yes
Roof Condition
Does the roof structure appear to be structurally sound, without signs of alterations
or significant structural deterioration or sagging?
Yes
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 17/30
NEC 2020 PV (rev_k)
ELECTRICAL DETAILS
Equipment
Inverter 1
What is the maximum fuse rating allowed on Inverter 1?20 A
Inverter 1 Model Number IQ7HS-66-M-US [240V]
Datasheet for Inverter 1: See attached. [NEC 90.7; 110.3(C)][IRC R106.1]1686953268688-I9-Enphase
microinverter specs.pdf
Inverter 1 Manufacturer:Enphase Energy Inc.
Is Inverter 1 UL 1741 listed? [NEC 110.3(C); 690.4(B)][IRC R324.3.1]Yes
Inverter 1 Maximum Continous Output Power 0.384 kW
Architecture type used for all inverters in this project Microinverters
Inverter 2
Inverter 2 Maximum Continous Output Power 0 kW
Modules
Module 1 Model Number Q.PEAK DUO BLK ML-G10+ 405
Datasheet for Module 1: See attached. [NEC 90.7; 110.3(C)][IRC R106.1]1686953500131-I12-Qcell 405
specs.pdf
Module 1 Manufacturer Hanwha Q CELLS
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 18/30
NEC 2020 PV (rev_k)
Modules
Is Module 1 UL 1703 or UL 61730 (Part 1 & 2) listed? [NEC 110.3(C); 690.4(B)][IRC
R324.3.1]
Yes
Module 1 quantity 11
Module open circuit voltage with record low temperature correction 48.6 V
Module short circuit current with average high temperature correction 13.96 A
Is the PV module bifacial?No
Module fire rating type 2
Racking System
Racking System Model Number InvisiMount
Racking System Manufacturer SunPower
Datasheet for Racking System: See attached. [NEC 90.7; 110.3(C)][IRC R106.1]1684268173114-I15-SPWR
Invisimount Specs.pdf
Is the Racking System UL 2703 listed for grounding and bonding with the PV module
models specified in this SolarAPP project? [NEC 90.7; 110.3(C); 690.43(A)][IRC
R324.4.2; R902.4]
Yes
The combination of modules and racking system shall have the same fire
classification as the roof assembly. [IRC R324.4.2; R902.4]
Yes
Name/description of roof penetration sealant method to be used.falshing
You have agreed to install the sealant method per the manufacturer's instructions for
the means of accomplishing weather proofing [IRC R324.4.3]
Yes
Fire classification [IRC R324.4.2]A
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 19/30
NEC 2020 PV (rev_k)
Racking System
Compatible roof pitch regime Both
Compatible module fire rating types 1
2
Maximum gap between the roof and the lowest point of the module 4 in
Compatible Roof Types Asphalt or composition shingles
Clay and concrete tile
Slate and slate-type shingles
Metal roof shingles or panels
Mineral-surfaced roll roofing
Wood shingles or Wood shakes
Built-up roofs
Modified bitumen roofing
Thermoset/Thermoplastic single-
ply roofing
Sprayed polyurethane foam
roofing
Liquid applied roofing
Rapid Shutdown
The AC module, microinverter, or DCDC converter installed on each module is listed
for UL 1741 or UL 3741 as PVRSS or PVRSE and used to comply with requirements
for Rapid Shutdown both inside and outside the array. [NEC 690.12]
Yes
Site Conditions
Ambient Dry Bulb Extreme Record Low Temperature (°C) [690.7(A)]-2 °C
Ambient Dry Bulb Average High Temperature (°C)32 °C
Single Phase Grid Voltage 240 V
Installation Details
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 20/30
NEC 2020 PV (rev_k)
Is there an existing Utility interactive power production source connected to the
home's electric service?
No
Are DC and AC conductors copper, Class B or Class C, and THWN-2, NM, USE-2,
PV Wire, or jacketed multiconductor cable assembly listed and identified for the
application? [NEC 690.8(B); 690.31 (A) & (C), 310.15(A) and (B)]
Yes
NM cable is used for inverter output circuits and installed in locations and uses
according to the Code [NEC 334.10]
Yes
Are all rooftop conduits mounted at least 7/8" above the roof surface [NEC
310.15(B)(2)]:
Yes
Are all power terminals rated to 75°C or greater, labeled for use with Copper Class
B or Class C wires, and accept at least 8 AWG wire? [NEC 110.14]
Yes
Where Equipment Grounding Conductors (EGC) or Grounding Electrode Conductors
(GEC) are not routed with circuit conductors, they are a minimum of 6 AWG or they
are protected from physical damage [250.120(C); 250.64(B)(3)]
Yes
Module voltage and current DC specifications fall within allowable range of
connected equipment
Yes
All equipment is listed for the application, rated equal to or greater than the
connected overcurrent device and installed per the manufacturer's instructions.
Documentation shall be provided at time of inspection.
Yes
Is there a utility available fault current greater than 10kA at the service?Yes
Installed equipment and OCPDs are either rated to 22kAic or protected sufficient
wire length to reduce the AFC to less than 10kA
Yes
Are all conductors installed without raceway listed as PV Wire, USE-2 or Type
distributed generation (DG) cable? [NEC 690.31(C)(1)]
Yes
Equipment Point of Interconnection
PV Source Circuit
How many modules does a single microinverter accept?1
How many microinverters are you installing 11
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 21/30
NEC 2020 PV (rev_k)
Point of Connection
Microinverter quantity multiplier (1 for string inverters)11
Sum of the PV inverters continous output current 17.6 A
125% of the sum of power production sources continuous output current.22 A
Will all power production inverter outputs have the same point of connection?Yes
At the time of inspection, it will be verified that if connected equipment is NOT within line of sight or closer than 10ft to the
point of interconnection, disconnect or isolation means are installed. [NEC 690.15 (A)]
Microinverter
PV Source Circuit
Microinverter maximum input DC open circuit voltage (Voc)59 V
Microinverter maximum input DC short circuit current (Isc)15 A
Inverter Output Circuit
Maximum number of Microinverters in a single branch (cannot exceed 16A
continuous, applicable to 20A breaker) [NEC 690.8(A)(1)(e); 690.9(B)]
6
You have selected to size all individual microinverter branch circuit OCPD to 20A Yes
Calculated Inverter Branch Continuous Output current based of inverter Maximum
Continuous Output Power at Unity Power Factor, Maximum number of
microinverters in a single branch, and site voltage.
10 A
Inverter Branch Continuous Output current used for sizing inverter output circuits
[NEC 220.5(B)]
16 A
See Table 3 for selection of minimum Inverter output wire size and inverter output overcurrent protection size.
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 22/30
NEC 2020 PV (rev_k)
Inverter Output Circuit
Calculated Branch Overcurrent Protective Device rating, from Table 3 based on the
total sum of inverter continuous output current ratings of parallel connected
microinverters. [NEC 705.30]
20 A
Combined Inverter continuous output current 17.6 A
Maximum number of THWN-2 conductors in a raceway from the solar arrays to the
OCPD, excluding any equipment grounding conductors
2
Branch wire size in raceway 12 AWG
Branch wire size for NM cable 12 AWG
Table 3 [NEC 240.4(D); table 310.15(C)(1); table 310.15(B)(2); table 310.16; 690.8; 690.9; 705.30; 220.5 (B)]
Continuous Output Current 12.5 16.5 20.5 24.5 28.5 32.5 36.5 40.5 48.5 56.5 64.5 72.5 80.5 88.5 100.
5
120.
5
140.
5
160.
5
OCPD amperage size 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200
AWG wire size for <=3 CCC in
raceway
12 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
AWG wire size for 4 - 6 CCC
in raceway
12 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
AWG wire size for 7 - 9 CCC
in raceway
12 12 10 10 8 8 8 6 6 4 4 3 3 2 1 2/0 3/0 4/0
NM wire 12 12 10 10 8 8 6 6 4 4 3 2 1 1 1/0 N/A N/A N/A
[240.4(D); Table 310.15(B)(3)(a) ; Table 310.15(B)(2)(b) ; Table 310.15(B)(16) ; 690.8; 690.9; 705.30]
Grounding & Bonding
See Table 5 for selection of Equipment Grounding Conductor wire gauge.
Branch - Equipment Grounding Conductor (EGC) based on overcurrent protective
device
12 AWG
Table 5 [NEC Table 250.122]
OCPD rating (amperes)EGC wire gauge (AWG)
=< 15 14
=< 20 12
=< 30 10
=< 40 10
=< 60 10
=< 100 8
=< 200 6
[Table 250.122]
Electrical Work
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 23/30
NEC 2020 PV (rev_k)
Main Panel Upgrades and Main Breaker Derates
A Main Panel Upgrade is being performed.No
A Main Breaker Derate is being performed.No
Busbars
Busbar quantity 2
Busbar 1
Busbar name Existing Main Service Panel
Is this a combiner panel?No
Is this an existing busbar?Yes
Select the type of existing busbar Main Service Panel
Ratings
Existing Main Service Panel busbar ampere rating 225 A
Rating of the OCPD protecting the Existing Main Service Panel 200 A
Feeder Interconnection
Are you connecting your power production sources to the Existing Main Service
Panel feeders at a location other than the downstream end of the feeder? [NEC
705.12 (B) (3) (6); 705.12 (B) (1) (a); 705.12 (B) (1) (b)]
N/A
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 24/30
NEC 2020 PV (rev_k)
Interconnection compliance
Generation sources connected on the load side of the feeder OCPD to the Existing
Main Service Panel
Yes
Generation sources are connected directly to the Existing Main Service Panel Yes
Compliance method for the Existing Main Service Panel 120% rule
Busbar 2
Busbar name PV Combiner Panel
Is this a combiner panel?Yes
Is this an existing busbar?No
Relocated Loads Panel
Will you relocate one or more existing loads to the new busbar?No
Combiner Panel
Will you use this new busbar for combining generation sources output?Yes
Do you have a dedicated OCPD protecting this busbar?No
Ratings
PV Combiner Panel busbar ampere rating 100 A
Feeders
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 25/30
NEC 2020 PV (rev_k)
Feeders
The length of the section of the PV Combiner Panel feeders that is inside a raceway
is less than or equal to 2 feet
Yes
Combined continous inverter output current on the PV Combiner Panel 17.6 A
See Table 3 for the minimum OCPD rating protecting the PV Combiner Panel 25 A
OCPD rating used to calculate the PV Combiner Panel feeders rating 25 A
The busbar rating is equal to or higher than 125% of the combined continous inverter output current.
Table 3
Continuous Output Current 12.5 16.5 20.5 24.5 28.5 32.5 36.5 40.5 48.5 56.5 64.5 72.5 80.5 88.5 100.
5
120.
5
140.
5
160.
5
OCPD amperage size 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200
AWG wire size for <=3 CCC in
raceway
12 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
AWG wire size for 4 - 6 CCC
in raceway
12 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
AWG wire size for 7 - 9 CCC
in raceway
12 12 10 10 8 8 8 6 6 4 4 3 3 2 1 2/0 3/0 4/0
NM wire 12 12 10 10 8 8 6 6 4 4 3 2 1 1 1/0 N/A N/A N/A
[240.4(D); Table 310.15(B)(3)(a) ; Table 310.15(B)(2)(b) ; Table 310.15(B)(16) ; 690.8; 690.9; 705.30]
Based on Table 23, calculated conductor gauge for the PV Combiner Panel feeders 10
Table 23
Feeder OCPD
amperage size 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200
Feeder OCP =
Service rating N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 4 2 2 1 1/0 2/0
Feeder raceway < = 2
14 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
=<3 CCC in feeder
raceway 14 12 10 10 8 8 8 8 6 4 4 3 3 2 1 1/0 2/0 3/0
4-6 CCC in feeder
raceway 14 12 10 10 8 8 6 6 6 4 3 3 2 1 1/0 2/0 3/0 4/0
7-9 CCC in feeder
raceway 14 12 10 8 8 6 6 6 4 3 3 2 1 1/0 2/0 3/0 4/0 Not
Com
patibl
e
[240.4(D); Table 310.15(B)(3)(a) ; Table 310.15(B)(2)(b) ; Table 310.15(B)(16) ; 690.8; 690.9; 705.30]
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 26/30
NEC 2020 PV (rev_k)
Feeder Interconnection
Are you connecting your power production sources to the PV Combiner Panel
feeders at a location other than the downstream end of the feeder? [NEC 705.12 (B)
(3) (6); 705.12 (B) (1) (a); 705.12 (B) (1) (b)]
N/A
Ground
Equipment Grounding Conductor size for the PV Combiner Panel 10 AWG
Table 5 [NEC Table 250.122]
OCPD rating (amperes)EGC wire gauge (AWG)
=< 15 14
=< 20 12
=< 30 10
=< 40 10
=< 60 10
=< 100 8
=< 200 6
[Table 250.122]
Raceway
Raceway size for the new busbar feeders is compliant with 300.17 and Chapter 9
[NEC 300.17; Chapter 9]
Yes
Interconnection compliance
Generation sources connected on the load side of the feeder OCPD to the PV
Combiner Panel
N/A
Interconnection compliance method at Busbar 1
120% Rule
Where two sources, one a primary power source and the other another power source, are located at opposite ends of a
busbar that contains loads, the sum of 125 percent of the power source(s) output circuit current and the rating of the
overcurrent device protecting the busbar shall not exceed 120 percent of the ampacity of the busbar. 705.12(B)(3)(2)
Service
Service OCPD Location Existing Main Service Panel
Service OCPD Rating 200 A
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 27/30
NEC 2020 PV (rev_k)
Service OCPD is greater than 100A
Utility Service Rating 225 A
Point of Connection at Service Feeders
Supply Side Connection
Are you connecting your power production sources in a supply side connection in
accordance with [NEC 705.11]?
No
Supported Tie-Ins
The point of interconnection is at the existing subpanel No
A PV Sub Panel Insert for load relocation from the main service panel to the new
load center is being installed in order to create space for the backfeed breaker.
No
The point of interconnection is at a subpanel feeder No
Main Service Panel type Regular
Combiner Panel Configuration PV
The busbar quantity per busbar category is aligned with the list of SolarAPP supported tie-ins.
A Main Service Panel has been found in the busbar inputs.
The MSP has been verified for backfeed compliance.
SolarAPP Supported Tie-Ins ID 12
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 28/30
NEC 2020 PV (rev_k)
WORKERS' COMP
By applying for this permit, you represent and warrant that youhave (and will have during the performance of the work) all
valid approvals, certifications, and licenses required for the performance of the work for which this permit is issued, (ii)
carry (and will carry during the performance of the work) all necessary insurance required by law or governmental authority
in the jurisdiction and (iii) will comply with all applicable laws required in the performance of the work.
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 29/30
NEC 2020 PV (rev_k)
SolarAPP PV Eligibility 09/08/2022
System
New Rooftop Residential Retrofit PV Systems
Installed by contractor with all licenses required by jurisdiction
Each residence must have a unique utility meter
Electrical
Applicable National Electric Code
600V Max per DC System Size
Single phase 240 V only
No Aluminum Wires
Must Use 600V rated PV wire (due to outer diameter > 0.24" (6.1mm))
Must use 90 deg C rated insulated wire
Max 2 DC strings in parallel
Max 9 current carrying conductors in a raceway
Inverter output circuit conductors must be THWN-2, or listed NM
Terminals must be rated to 75 deg C, labeled for use with Cu wires, and accept minimum 8 AWG wire
Whenever used, the microinverters or AC Modules branch circuit overcurrent protection device must be rated for a maximum of 20A
Permitted to install on up to or equal to 400A Service
Permitted to install on up to or equal to 225A Service Disconnect
Permitted to install on up to or equal to 225A busbars
No existing PV or ESS
May install only 1 module type
May install up to 2 Inverters for String Inverters, up to 1 inverter type for Micro-inverters and AC modules Systems
Conduit may not be Schedule 80 PVC
Modules and Inverters must be listed on CEC
Rapid Shutdown cannot be satisfied using the method: No exposed wiring or conductive parts [690.12(B)(2)(3)]
No trenching allowed
All power production inverter outputs have the same point of connection
No new loads, only new monitoring loads are allowed
All equipment is assumed to be non-continuous rated
May install only 1 racking system type
Height of rooftop conduit > = 7/8"
Flat Plate PV Modules Only
Structural
Detached one- and two-family dwellings and townhomes not more than three stories above grade plane in height with a separate means of egress
Accessory structures to one- and two-family dwellings and townhomes not more than three stories above grade plane in height
Penetrations within 4 ft of the fire-rated property line on the roof of a townhome shall not be permitted
Installations in multi-family structures or R-2 occupancies shall not be permitted
Installations on mobile homes governed by Heath and Safety Code and/or Housing and Urban Development regulations shall not be permitted.
Applicable International Residential Code
PV system + hardware weight is less than or equal to 4psf
No ground mounted systems
No carports or non-permanent structures
No modification alterations or upgrades to the structure
At least 20% of each tilt-up mounted array must be contained under 2 feet above the roof
Installed on a permitted structure
No wood shake or wood shingle roofing
Limit of 10" above the roof for pitched (>2/12) roof systems
No metal roof or low-slope roof in areas with > 15psf snow load
Fire
Applicable International Residential Code
Powered by TCPDF (www.tcpdf.org)
Approval ID: SA20230823-2142-233-1576-A
Reviewed for Code compliance
08-23-2023
SolarAPP+
City of San Luis Obispo, CA
Page 30/30
NEC 2020 PV (rev_k)