HomeMy WebLinkAbout849 higuera 2 $Inspection-Letter_09-08-2026 2160 Santa Barbara Avenue, San Luis Obispo, CA 93401
Phone: (805) 783 - 7775 Fax: (805) 543 - 8019 Fire Department Email: FDGeneral@slocity.org
Hours: Monday - Friday, 8:00 am - 5:00 pm
Business / Occupant:WINEMAN HOTEL Address:849 Higuera
Work Phone:
Contact Name:Stevenson, Gary Email:Gary@peakslo.com
Date Completed:03/23/2026 Inspected By:Thomas, Brandon
Passed:No Violation Count:4
San Luis Obispo City Fire Inspection Report
Fire Department Information
Business / Occupant Information
Inspection Information
Thank you for your cooperation with San Luis Obispo City Fire in keeping your business and our community safe!
Correct the cited violation(s) by the "Reinspection Date" listed below to avoid further enforcement action including, but
not limited to, chargeable re-inspection and/or Administrative Citation. You may request a review of the cited violations by
the Department Director [Fire Chief ] within 5 days of report issuance if noted violations do not create an immediate danger
to health and safety (SLO M.C. 1.24.090).
If you have any questions, please contact our Inspection Line at 805/783-7775.
Inspection Notes:SLO Fire Department followed up on a tenant complaint concerning Fire and Life Safety Systems at
849 Higuera Street on 03/23/2026 at 09:55 AM with Property Owner Gary Stevenson.
Note: Thank you for addressing gas meter utility identification and installing an approved cover over
the electrical junction box (located at the Fire Sprinkler Riser back wall).
Property Management is directed to address the following items at this property before follow-up
inspection:
1. The Fire Sprinkler Riser (located in building 847 Higuera, Corazon Café) was found with the chain
and padlock cut/removed from the 3 tamper switches (please see attached photos). Property
Management is directed to reinstall the chains and locks to secure the tamper switches, according to
(CFC 901.4.7.1 access).
2. Apt #229 smoke detector found non-operational during inspection. Please repair and/or replace
the smoke detector life safety system in accordance with (CFC 901.8 Removal of or Tampering with
Equipment).
Note: While performing the inspection in Apt. #229, apparatuses used for smoking were observed on
a nightstand next to the bed. Per Property Management, "The tenant will be issued a tenant citation
for violating the tenant lease agreement". Property management is recommended to reinforce the
no-smoking policy.
Note: Due to prior occupancy, not all dwelling units were accessible during the inspection. Property
Management is directed to provide a record of completion of the inspection and maintenance log for
all smoke detectors in each unit, and to test them regularly and routinely.
A reinspection will occur 30 days after the initial inspection for Item #1 and 7 days for Item #2. If you
have any questions about violations or re-inspections, please get in touch with Inspector Brandon
*Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and
every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by
you in court.Page 1 of 3
Thomas at Bthomas@slocity.org or (805) 634-8314.
Violations
Code Description Comments Reinspection Date Repaired Date
901.4.7.1 Access.
Automatic sprinkler
system risers, fire
pumps and
controllers shall be
provided with ready
access. Where
located in a fire pump
room or automatic
sprinkler system riser
room, the door shall
be permitted to be
locked provided that
the key is available at
all times.
1) The Fire Sprinkler
Riser (located in
building 847 Higuera,
Corazon Café) was
found with the chain
and padlock
cut/removed from
the 3 tamper
switches (please see
attached photos).
Property
Management is
directed to reinstall
the chains and locks
to secure the tamper
switches, according
to (CFC 901.4.7.1
access).
04/27/2026
603.2.2 Open electrical
terminations.
Open junction boxes
and open-wiring
splices shall be
prohibited. Approved
covers shall be
provided for all
switch and electrical
outlet boxes.
2) An electrical
junction box (located
in building 847
Higuera, Corazon
Café) found at the
Fire Sprinkler Riser
room wall, missing an
approved cover with
exposed wiring.
Please reinstall an
approved electrical
junction box cover in
accordance with (CFC
603.2.2 Open
Electrical
Terminations).
04/27/2026 03/23/2026 12:21:45
509.1.1 Utility identification.
Where required by
the fire code official,
gas shutoff valves,
electric meters,
service switches and
other utility
equipment shall be
clearly and legibly
marked to identify
the unit or space that
it serves.
Identification shall be
made in an approved
manner, readily
visible and shall be
maintained.
3) Label gas meters
with the
corresponding units
served. Property
management is
directed to contact
the gas company and
label all gas meters
with the
corresponding
address(s) served
according to (CFC
509.1.1 Utility
Identification).
04/27/2026 03/23/2026 12:21:33
901.8 Removal of or
tampering with
equipment.
It shall be unlawful
for any person to
remove, tamper with
or otherwise disturb
any fire protection or
life safety system
2. Apt #229 smoke
detector found non-
operational during
inspection. Please
repair and/or replace
the smoke detector
life safety system in
accordance with (CFC
901.8 Removal of or
04/27/2026
*Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and
every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by
you in court.Page 2 of 3
required by this code
except for the
purposes of
extinguishing fire,
training, recharging
or making necessary
repairs or where
approved by the fire
code official.
Tampering with
Equipment).
Note: While
performing the
inspection in Apt.
#229, apparatuses
used for smoking
were observed
located on a
nightstand next to
the bed. Per Property
Management, "The
tenant will be issued
a tenant citation for
violating the tenant
lease agreement".
Property
management is
recommended to
reinforce the no-
smoking policy.
Note: Due to prior
occupancy, not all
dwelling units were
accessible during the
inspection. Property
Management is
directed to provide a
record of completion
of the inspection and
maintenance log for
all smoke detectors in
each unit, and to test
them regularly and
routinely.
Inspection Documents
Violation Documents
*Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and
every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by
you in court.