HomeMy WebLinkAbout1118 Chorro Fire ReportIncident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
Incident Number:26-06225
Shifts or Platoon:B
Dispatch Point:35.279582,-
120.662481
Call Arrival:09/27/2026
06:17:32
Call Answered:09/27/2026
06:17:32
Call Created:09/27/2026
06:17:32
Alarm:09/27/2026
06:18:26
First Unit Arrival:09/27/2026
06:23:13
Incident Clear:09/27/2026
08:28:03
In Service:09/27/2026
07:10:35
Zone Number:FZ1
Dispatched Location:1118 CHORRO
City, State, Postal Code:San Luis Obispo, CA 93401
Incident Date:09/27/2026 Incident Point:35.279582,-
120.662481
Incident Number:26-06225 Incident Date:09/27/2026
Deploy NERIS Print Report
Details Reported by Dispatch
Dispatch Timeline
Location as Reported by Dispatch
Unit Response as Reported by Dispatch
Dispatch Unit Responses
Dispatch
Unit NERIS
ID
Dispatch
Unit
Name
Dispatch
Unit
Staffing
Reported
Dispatch
Unit
Dispatch
Time
Dispatch
Unit Enroute
to Scene
Time
Dispatch
Unit on
Scene Time
Dispatch
Unit
Incident
Clear Time
Dispatch
Apparatus or
Resource In
Service Date
Time
FD0607908
6S006U006
BC2 1 06:18:26 06:20:07 06:23:13 08:27:01 08:27:01
FD0607908
6S006U016
T1 4 06:18:26 06:21:20 06:23:41
FD0607908
6S007U000
E4 3 06:18:26 06:20:34 06:26:07
FD0607908
6S006U014
T2 3 06:18:26 06:21:00 06:29:36 07:42:11 07:42:11
FD0607908
6S008U002
E3 3 06:18:26 06:21:53 06:26:54
FD0607908
6S006U022
PRV20 07:17:03 07:18:47 08:28:03 08:28:03
Incident Details
Page 1 of 6
Incident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
NERIS Incident ID:FD06079086|26-
06225|1790515
052
Incident ID:26-06225
Primary Incident Type:Fire - Structure Fire - Room and Contents Fire
Response Mode To Scene:Code 3
Primary Station:Fire Station 1
(FS1)
Shifts or Platoon:B
Alarms:1 Fire Ser vice Casualties / Rescues:0
People Present:Yes Civilian Casualties / Rescues:0
People Displaced:0 Animals Rescued:0
Displaced People Cause:Smoke
Alarm:09/27/2026
06:18:26
First Unit Arrival :09/27/2026
06:23:13
Incident Clear:09/27/2026
08:28:03
In Service Date Time:09/27/2026
07:10:35
Zone Number:FZ1
Incident Location:1118 CHORRO
City, State, Postal Code:San Luis Obispo, CA 93401-
Location Use Type:Commercial - Restaurant / Cafe
Incident Location In Use:Yes
Location Used as Intended:Yes
Incident Location Secondary Use:Residential - Multi-Family Lowrise Dwelling
(<=4 Stories)
Incident Action Taken:Command and Control - Establish Incident
Command; Suppression - Structural Fire
Suppression - Interior; Ventilation - Positive
Pressure - Post Suppression
Member Making Report - Signature:Hoover,
Nicholas
Officer in Charge - Signature:Hoover,
Nicholas
Member Making Report:46955 Officer in Charge:46955
Incident Number:26-06225 Incident Date:09/27/2026
Incident Timeline
Incident Location
Incident Location Use
Incident Actions
Incident Authorization
Incident Narratives
Primar y Narrative:First alarm response to the report of a structure fire at Sweet Cup Tea. BC2
arrived at scene and established Chorro IC, reporting a three story structure with
two residential stories over a business, with a small fire showing behind the glass
at the front of the occupancy. 360 was completed, low victim profile, T2 arrived
at scene and was assigned to extinguish the fire using a water can through the
window area that had blown out from heat. T1 arrived at scene and was assigned
division 1, with the objective of overhauling the fire, primary/secondary all clear
and containing the fire sprinkler. E4 arrived at scene and was assigned division 2,
with the objective of checking for smoke and extension on the 2nd and 3rd floor,
Page 2 of 6
Incident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
Incident Number:26-06225 Incident Date:09/27/2026
and silencing the fire alarm system. Division 1 reported back that they had
knockdown, and primary/secondary all clear, the business was not open at the
time of the incident. Division 2 reported light smoke in the upper apartments,
and E3 was assigned to assist them with ventilation and restoring the fire alarm
systems. E3 was able to shut down the riser, division 1 had already wedged the
fire sprinkler shut to limit water damage. Investigator, water standby, building
official, fire protection contractor and county environmental health standby
requested. Fire and life safety systems were restored to the second and third
floors by division 2 and the contractor, no occupants were displaced, smoke was
cleared and building was reoccupied. Environmental health standby made
appropriate notifications to the county food inspector. Property manager arrived
at scene, responsible party was not able to be reached. Property manager took
possession of the building. Fire investigator completed investigation, see
additional narrative. Command was terminated, all units available.
Additional Narrative
Additional Narratives Authored By
Authored
Date
T1 arrived at scene, T1 given Division 1 assignment. T1 crew assisted with Knox box
location for entry master key. T1 crew assisted T2 crew with fire attack. Operator 1
was able to locate fire riser on Bravo side in retail/cafe store to shut down and isolate
affected sprinkler head. T1 crew overhaul/salvage, utilized water backpack for interior
floor clean up. T1 assisted Fire Investigator with any requested needs. T1 released
once property manager was at scene and updated on all information.
Page 3 of 6
Incident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
Incident Number:26-06225 Incident Date:09/27/2026
Additional Narratives Authored By
Authored
Date
INVESTIGATION
My investigative actions and findings are based on a scientific examination of the
fire's origin and cause.
Methodology
The methodology I utilized during this investigation consisted of identifying all
available data for origin determination, including witness accounts, an initial scene
assessment, development of a preliminary fire spread hypothesis, an in-depth
examination of the fire scene, reconstruction of the fire scene, development of a final
fire spread hypothesis, and identification of the fire’s origin.
I identified all available data for cause determination, including ignition sources, fuel
packages, oxidizers, and circumstances. I used all available resources to develop fire-
cause hypotheses and determine which best fit the credible data to identify the cause
of this fire.
Area of Origin (AOO)
After careful consideration, and after accounting for all credible data and eliminating
all credible alternate origin hypotheses, it is my opinion that the area of origin was the
immediate area of the electrical receptacle and surge protector where the surge
protector was connected to the building’s electrical system.
AOO Fire Patterns
Fire patterns observed within the area of origin were consistent with fire
development originating at or near the surge protector and electrical receptacle. The
most significant fire effects and damage were concentrated in the immediate vicinity
of the surge protector, with fire effects decreasing as distance increased from this
area. The observed damage and fire patterns were consistent with a low-level fire
originating near the surge protector and subsequently extending to nearby
combustible materials.
The observed fire patterns, physical damage, and available scene information were
evaluated collectively when determining the area of origin. No fire patterns or other
physical evidence supported an alternate area of origin.
AOO Competent Ignition Sources
Within the identified area of origin, the electrical receptacle and the surge protector
connected to the receptacle were identified as potential competent ignition sources.
The surge protector was connected to the energized building electrical system and
was being used to supply electrical power to multiple electrical devices.
Based on the physical evidence, scene examination, and available information, the
surge protector was determined to have been subjected to an electrical load
exceeding its intended capacity. The resulting electrical condition generated
sufficient thermal energy to ignite combustible materials associated with or
immediately adjacent to the surge protector.
The investigation considered other reasonably identifiable competent ignition
sources within the area of origin. Based on the available evidence, no other
competent ignition source reasonably explains the ignition and subsequent fire
development.
IGNITION SOURCE: Heat generated by a high-resistance electrical connection.
MATERIAL FIRST IGNITED: Combustible components/materials immediately adjacent
to the failed electrical connection.
OXIDANT: Oxygen from the surrounding air.
EVENT: A high-resistance electrical connection generated sufficient heat to thermally
degrade and ignite adjacent combustible material.
Joshua Daniel Fire
Marshal
14:57:14
Unit Response
Incident Unit Responses
Page 4 of 6
Incident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
Fire Location Type:Structure Fire Investigation Needed:Yes
Fire Water Supply:None Fire Investigation Type:Investigated By
Arson Fire
Investigator
Incident Number:26-06225 Incident Date:09/27/2026
Unit NERIS ID
Unit
Name
Apparatus
ID
Unit
Staffing
Reported
Apparatus
Action
Unit
Dispatch
Time
Unit
Enroute
to
Scene
Time
Unit on
Scene
Time
Unit
Incident
Clear
Time
Apparatus
or
Resource
In Service
Date Time
FD06079086S007U000 E4 E4 3 06:18:26 06:20:34 06:26:07
Incident Unit Response Personnel
Personnel Name/ID Personnel Rank Or Grade Personnel Time In
McClanahan, Maren Firefighter 09/27/2026 06:18:26
Pratt, Jason Captain 09/27/2026 06:18:26
Johnston, Kenneth Engineer 09/27/2026 06:18:26
FD06079086S006U006 BC2 BC2 1 06:18:26 06:20:07 06:23:13 08:27:01 08:27:01
Incident Unit Response Personnel
Personnel Name/ID Personnel Rank Or Grade Personnel Time In Personnel Time Out Personnel Hours Spent
Hoover, Nicholas Battalion Chief 09/27/2026 06:18:26 09/27/2026 08:27:01 2.14
FD06079086S006U016 T1 T1 4 06:18:26 06:21:20 06:23:41
Incident Unit Response Personnel
Personnel Name/ID Personnel Rank Or Grade Personnel Time In
Robertson, Travis Engineer 09/27/2026 06:18:26
Van De Walker, Gegi Firefighter 09/27/2026 06:18:26
Barrett, Richard Captain 09/27/2026 06:18:26
Hutslar, Dane Engineer 09/27/2026 06:18:26
FD06079086S008U002 E3 E3 3 06:18:26 06:21:53 06:26:54
Incident Unit Response Personnel
Personnel Name/ID Personnel Rank Or Grade Personnel Time In
Hicks, Judson Firefighter 09/27/2026 06:18:26
Witt, James Captain 09/27/2026 06:18:26
Sabatino, Jacob Engineer 09/27/2026 06:18:26
FD06079086S006U014 T2 T2 3 06:18:26 06:21:00 06:29:36 07:42:11 07:42:11
Incident Unit Response Personnel
Personnel Name/ID Personnel Rank Or Grade Personnel Time In Personnel Time Out Personnel Hours Spent
Woods, Mitchell Captain 09/27/2026 06:18:26 09/27/2026 07:42:11 1.4
Greenelsh, Nathaniel Firefighter 09/27/2026 06:18:26 09/27/2026 07:42:11 1.4
Joy, Cullen Engineer 09/27/2026 06:18:26 09/27/2026 07:42:11 1.4
FD06079086S006U022 PRV20 PRV20 1 Investigation 07:17:03 07:18:47 08:28:03 08:28:03
Incident Unit Response Personnel
Personnel
Name/ID Personnel Role
Personnel Time
In
Personnel Time
Out
Personnel Hours
Spent
Daniel, Josh IncidentUnitResponsePersonnelRole_Investigator 09/27/2026
07:17:03
09/27/2026
08:28:03 1.18
Fire Details
Page 5 of 6
Incident Location:1118 CHORRO Incident Date:09/27/2026
Incident City, State, Postal Code:San Luis Obispo, CA 93401
Fire Arrival Condition:Smoke Fire
Showing
Fire Floor Of Origin:1 Fire Room Of Origin Type:Kitchen
Fire Damage Type:Moderate
Damage
Structure Fire Cause:Electrical
Smoke Alarm Presence:Present Fire Alarm Presence:Present
Smoke Alarm Type:Interconnected Fire Alarm Type:Automatic
Smoke Alarm Working:Yes Fire Alarm Operation:Operated -
Alerted
Occupant(s)
Smoke Alarm Operation:Operated -
Alerted
Occupant(s)
Other Alarm Presence:Not Applicable
Fire Suppression Presence:Present
Incident Number:26-06225 Incident Date:09/27/2026
Structure Fire
Casualty/Rescue
People Involved
Risk Reduction
Fire Suppression
Fire Suppression Types
Fire Suppression Type
Wet Pipe Sprinkler System
Page 6 of 6