HomeMy WebLinkAbout08-10-2026 Inspection-Letter 2160 Santa Barbara Avenue, San Luis Obispo, CA 93401   Phone: (805) 783 - 7775 Fax: (805) 543 - 8019 Fire Department Email: FDGeneral@slocity.org    Hours: Monday - Friday, 8:00 am - 5:00 pm Business / Occupant:LAGUNA MIDDLE SCHOOL Address:11050 Los Osos Valley Road Work Phone:805-596-4105 Contact Name:Stewart, Stephan Email:rstimson@slcusd.org Date Completed:08/10/2026 Inspected By:Thomas, Brandon Passed:No Violation Count:16 San Luis Obispo City Fire Inspection Report Fire Department Information Business / Occupant Information Inspection Information Thank you for your cooperation with San Luis Obispo City Fire in keeping your business and our community safe! Correct the cited violation(s) by the "Reinspection Date" listed below to avoid further enforcement action including, but not limited to, chargeable re-inspection and/or Administrative Citation. You may request a review of the cited violations by the Department Director [Fire Chief ] within 5 days of report issuance if noted violations do not create an immediate danger to health and safety (SLO M.C. 1.24.090). If you have any questions, please contact our Inspection Line at 805/783-7775. Inspection Notes:The SLO Fire Department performed an Annual Fire and Life Safety Inspection at 11050 Los Osos Valley Road (Laguna Middle School) on 08/10/2026 at 09:00 AM with a representative of the San Luis Coastal Unified School District, Steve Stewart. Inspection Summary: The campus remains under active construction and renovation, with multiple buildings and areas affected. Several fire and life safety systems have been modified or affected by construction activities. All identified deficiencies shall be corrected before the beginning of the 2026–2027 school year. Documentation confirming that modified fire and life safety systems have been tested, restored, and returned to normal operation shall be provided to the Fire Department. Fire Protection System Records: A. Fire Alarm System: Last serviced July 24, 2026, by Alpha Fire Unlimited (C-10, C-16 #761360, ACO #5365). Current records indicate the system is compliant in The Compliance Engine. B. Automatic Fire Sprinkler System: Last serviced July 24, 2026, by Alpha Fire Unlimited (C-16 #761360). Current records indicate the system is compliant in The Compliance Engine. C. Private Fire Hydrants Last serviced July 24, 2026, by Alpha Fire Unlimited (C-16 #761360). Current records indicate the hydrant is deficient in The Compliance Engine. D. Commercial Kitchen Hood Suppression System: The Compliance Engine indicates the hood suppression system renewal expired August 1, 2025. No current inspection/service documentation was available. The system shall be serviced and *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 1 of 47 documentation uploaded to The Compliance Engine. Note: The kitchen hood exhaust system cleaning and inspection is also past due as of June 26, 2026. A qualified contractor shall complete cleaning before cooking operations resume. FIRE AND LIFE SAFETY DEFICIENCIES: 1. Fire Alarm System: Due to active construction, the Fire Alarm Control Panel (FACP) displayed multiple supervisory/trouble conditions. Full system operation could not be verified because construction activities may have affected system components. Required Correction: Upon completion of construction, have a qualified fire alarm contractor test the complete system and verify that it has been restored to normal operation. Provide the Fire Department with testing documentation and upload the applicable report to The Compliance Engine. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance The 2025 CFC specifically requires fire protection and life safety systems to be maintained in an operative condition and requires fire alarm systems to be tested and maintained in accordance with NFPA 72. 2. Private Fire Hydrants / Fire Department Connections: Private fire hydrant(s) are listed as deficient in The Compliance Engine. Required Correction: The contractor of record shall correct all deficiencies and upload a compliant inspection report to The Compliance Engine. Note: Construction plans indicate a new OS&Y/double-check assembly was installed on the west side of the property, with modifications to the domestic and fire service lines and removal of three existing FDCs. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance Note: Final verification of proper installation, accessibility, and operational readiness shall be completed following construction. 3. Newly Installed OS&Y / Double-Check Assembly: The new OS&Y/double-check assembly requires completion of the Fire Department Connection installation. Required Correction: Install the approved FDC connection, provide approved protective cap covers, and install the required chain and lock on the double-check/OS&Y valve assembly. 2025 CFC References: CFC 912.7 – Inspection, Testing and Maintenance 4. Commercial Kitchen Hood Suppression / Exhaust System: No current hood suppression inspection documentation was available in The Compliance Engine. The hood exhaust system cleaning is also past due as of 06/26/2026. Required Correction: Have the commercial kitchen hood suppression system serviced by a qualified contractor and upload the current inspection report to The Compliance Engine. The hood exhaust system shall be cleaned and inspected before cooking operations resume. 2025 CFC References: CFC 606.3.3 – Commercial Cooking Operations / Exhaust System Maintenance 5. Building G – Sprinkler Riser Room: The north sprinkler riser room was missing the required hydraulic calculation plate. Required Correction: Provide and properly install the required hydraulic design information/calculation plate at the sprinkler riser. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 2 of 47 NFPA 13, as referenced by CFC Table 901.6.1 – Hydraulic Design Information Sign Note: The sprinkler system shall retain the required hydraulic design information for identification and maintenance purposes. 6. Building Maintenance – Missing Ceiling Tiles: Missing ceiling tiles were observed throughout classrooms and other occupied spaces. Required Correction: Replace missing ceiling tiles and restore affected ceiling assemblies to their approved condition to maintain required fire-resistance characteristics and minimize smoke migration. 2025 CFC References: CFC 703.1 – Maintenance of Fire-Resistance-Rated Construction 7. Portable Fire Extinguishers: Portable fire extinguishers have been annually serviced but were not reinstalled in their designated locations. Required Correction: Reinstall all portable fire extinguishers in their designated and approved locations before occupancy. 2025 CFC References: CFC 906.1 – Where Required Note: The 2025 CFC requires portable fire extinguishers to be conspicuously located, readily accessible, and installed on approved hangers or brackets. 8. Welding Shop: The welding shop requires additional fire/life safety corrections. Required Correction: Install a smoke detector in the classroom. Replace the old/recalled natural gas connectors connected to the appliance located on the workbench. 2025 CFC References: CFC 907.10 – Smoke Alarm Maintenance, as applicable Note: Recalled or damaged equipment and components shall be corrected or replaced as required. The 2025 CFC requires unsafe electrical conditions to be abated and damaged or modified equipment constituting a hazard to be repaired or replaced. 9. Building C – Mechanical Room: Gas appliances previously installed in the mechanical room are no longer in service/use. Required Correction: Install appropriate identification/signage for gas appliances that have been removed from service or are no longer in use, as applicable, and ensure unused gas equipment is safely secured or removed. 2025 CFC References: CFC 605.1 – General, Fuel-Fired Appliances Note: The 2025 CFC prohibits continued operation of appliances whose operation has been discontinued or ordered discontinued unless authorized by the fire code official. 10. Annex Building – Basketball Gym: Exposed electrical outlets were observed. Required Correction: Install approved covers over all exposed electrical outlets and electrical boxes. 2025 CFC References: CFC 603.2.2 – Open Electrical Terminations The 2025 CFC specifically prohibits open junction boxes and open-wiring splices and requires approved covers for electrical and outlet boxes. *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 3 of 47 11. Means of Egress – Emergency Lighting and Exit Signs: The following deficiencies were observed: -Non-operational emergency exit lighting. -Missing exit signage due to construction. -Inoperative emergency "bug-eye" lighting fixtures. -Missing exit signage in classrooms. -Exit signs removed during construction have not been reinstalled. Required Correction: Repair or replace all inoperative emergency lighting and reinstall all required exit signs. Verify that all required exit signage and emergency lighting are operational before the beginning of the 2026–2027 school year. 2025 CFC References: CFC 1002.1 – Maintenance of Means of Egress CFC 1003.1 – Applicability CFC 1008.1 – Means of Egress Illumination CFC 1013.1 – Where Required, Exit Signs CFC 1013.3 – Illumination The 2025 code requires means of egress to be maintained and requires approved exit signs to be readily visible along the required egress path. Exit signs must also remain illuminated. Note: Construction / System Restoration Requirement: Due to active construction, all fire and life safety systems affected by construction shall be fully tested and restored before the beginning of the 2026–2027 school year. A reinspection will occur on Wednesday, 08/26/2026 at 9 am to observe fire drill evacuations and to address the remaining fire code violations. If you have any questions about violations or re- inspections, please contact Fire Inspector Thomas at Bthomas@slocity.org or (805) 634-8314. Violations Code Description Comments Reinspection Date Repaired Date 907.8 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with Sections 907.8.1 through 907.8.4 and NFPA 72. Records of inspection, testing and maintenance shall be maintained. Fire Alarm System: -Due to active construction, the Fire Alarm Control Panel (FACP) displayed multiple supervisory/trouble conditions. -System status could not be fully verified because construction activities may have temporarily affected system components. -A follow-up inspection will be required after construction is complete to verify proper operation. Reference: CFC Section 907.8 10/08/2026 315.3.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or not less than 18 inches (457 mm) below sprinkler head deflectors in Automatic Fire Sprinkler System: -Portions of the sprinkler system, piping, and risers were inaccessible due to construction. Complete inspection could not be performed. -Maintain a minimum 08/18/2026 08/10/2026 12:01:12 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 4 of 47 sprinklered areas of buildings. Exceptions: 1.The 2-foot (610 mm) ceiling clearance is not required for storage along walls in nonsprinklered areas of buildings. 2.The 18-inch (457 mm) ceiling clearance is not required for storage along walls in areas of buildings equipped with an automatic sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. clearance of 18 inches below sprinkler heads in storage rooms. Reference: CFC Section 315.3.1 606.3.3 Cleaning. Hoods, grease- removal devices, fans, ducts and other appurtenances shall be cleaned at intervals as required by Sections 606.3.3.1 through 606.3.3.3. Commercial Kitchen Hood Suppression / Exhaust System: No current hood suppression inspection documentation was available in The Compliance Engine. The hood exhaust system cleaning is also past due as of 06/26/2026. Required Correction: Have the commercial kitchen hood suppression system serviced by a qualified contractor and upload the current inspection report to The Compliance Engine. The hood exhaust system shall be cleaned and inspected before cooking operations resume. 2025 CFC References: CFC 606.3.3 – Commercial Cooking Operations / Exhaust System Maintenance 10/08/2026 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and California Code of Regulations, Title 19, Division 1, Portable Fire Extinguishers: The following deficiencies were noted: -All portable fire extinguishers were found past due for annual maintenance. -Portable fire 08/18/2026 08/10/2026 15:15:42 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 5 of 47 Chapter 3. Exceptions: 1.The distance of travel to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies. 2.Thirty-day inspections shall not be required for portable fire extinguishers that are supervised by a listed and approved electronic monitoring device, provided that all of the following conditions are met: 2.1.Electronic monitoring shall confirm that extinguishers are properly positioned, properly charged and unobstructed. 2.2.Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal. 2.3.The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4.Electronic monitoring devices and supervisory circuits shall be tested when extinguisher maintenance is performed. 2.5.A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by California Code of Regulations, Title 19, Division 1, Chapter 3. 3.In Group I-3, and in mental health areas of Group I-2, portable fire extinguishers shall be permitted to be located at staff locations. [California Code of Regulations, Title 19, extinguishers located within mechanical rooms require current annual certification. -Multiple extinguishers throughout construction areas were found resting on the floor rather than properly mounted. Reference: CFC Section 906.2 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 6 of 47 Division 1, §565.1(a) through (c)] Classification of Hazards. (a) Light (Low) Hazard. Locations where the total amounts of Class A combustible materials, including furnishings, decorations and contents, is of minor quantity. These shall include buildings or rooms occupied as offices, classrooms, churches, assembly halls, etc. This classification anticipates that the majority of the contents are either noncombustible or so arranged that a fire is not likely to spread rapidly. Small amounts of Class B flammables used for duplicating machines, art departments, etc., are included provided that they are kept in closed containers and safely stored. (b) Ordinary (Moderate) Hazard. Locations where the total amounts of Class A combustibles and Class B flammables are present in greater amounts than expected under Light (Low) Hazard occupancies. These occupancies could consist of offices, classrooms, mercantile shops and allied storage, light manufacturing, research operations, auto showrooms, parking garages, workshop or support service areas of Light (Low) Hazard occupancies, and warehouses containing Class I or Class II commodities. (c) Extra (High) Hazard. Locations where the total amount of Class A combustibles and *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 7 of 47 Class B flammables are present, in storage, production use, and/or finished product over and above those expected and classed as Ordinary (Moderate) Hazards. These occupancies could consist of woodworking, vehicle repair, aircraft and boat servicing, individual product display showrooms, product convention center displays, storage and manufacturing processes such as painting, dipping, coating, including flammable liquid handling. Also, included in warehousing of, or in- process storage of other Class I and Class II commodities. [California Code of Regulations, Title 19, Division 1, §565.2(a) through (e)] Selection by Hazard. (a) Extinguishers shall be selected for the specific class or classes of hazards to be protected in accordance with the following subdivisions (b), (c), (d) and (e). (b) Extinguishers for protecting Class A hazards shall be selected from the following: Water- type, halogenated agent types, multipurpose dry chemical and wet chemical type. (c) Extinguishers for protection of Class B hazards shall be selected from the following: carbon dioxide, dry chemical types, halogenated agent types and water-type and water chemical extinguishers rated for Class B hazards. (d) Extinguishers for protection of Class C *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 8 of 47 hazards shall be selected from the following: carbon dioxide, dry chemical types, halogenated agent types and water mist types rated for Class C. Carbon dioxide extinguishers equipped with metal horns are not considered safe for use on fires in energized electrical equipment and, therefore, are not classified for use on Class C hazards. (e) Extinguishers and extinguishing agents for the protection of Class D hazards shall be of types approved for use on the specific combustible metal hazard. [California Code of Regulations, Title 19, Division 1, §566(a) through (f)] Application for Specific Hazards. (a) Class B Fire Extinguishers for Pressurized Flammable Liquids and Pressurized Gas Fires. Fires of this nature are considered to be a special hazard. Class B fire extinguishers containing agents other than dry chemical are relatively ineffective on this type of hazard due to stream and agent characteristics. Selection of extinguishers for this type of hazard shall be made on the basis of recommendations by manufacturers of this specialized equipment. The system used to rate extinguishers on Class B fires (flammable liquids in depth) is not applicable to these types of hazards. It has been determined that special nozzle design and rates of *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 9 of 47 agent application are required to cope with such hazards. Caution: It is undesirable to attempt to extinguish this type of fire unless there is reasonable assurance that the source of fuel can be promptly shut off. (b) Fire extinguishers provided for the protection of cooking appliances that use combustible cooking media (vegetable or animal oils and fats) shall be listed and labeled Class K fires. (c) Three-dimensional Class B Fires. A three- dimensional Class B fire involves Class B materials in motion such as pouring, running or dripping flammable liquids and generally includes vertical as well as one or more horizontal surfaces. Fires of this nature are considered to be a special hazard. Selection of extinguishers for this type of hazard shall be made on the basis of recommendations by manufacturers of this specialized equipment. The system used to rate extinguishers on Class B fires (flammable liquids in depth) is not directly applicable to this type of hazard. (d) Water Soluble Flammable Liquid Fires (Polar Solvents). Extinguishers used for the protection of water soluble flammable liquids, such as alcohols, acetones, esters, ketones, etc., shall be selected in accordance with Section 565.2. AFFF- type and FFFP-type fire extinguishers shall not be used for the protection of water soluble *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 10 of 47 flammable liquids, such as alcohols, acetone, esters, ketones, etc., unless specifically referenced on the extinguisher nameplate. (e) Electronic Equipment Fires. Extinguishers for the protection of delicate electronic equipment shall be selected from the following: carbon dioxide type or a halogenated agent type, or a distilled water mist type with a minimum Class A:C Rating. (f) In patient care areas and sleeping rooms of health care facilities, fire extinguishers, including the agents and expelling means, should be selected and utilized that would not be detrimental to patients and are appropriate for the type of fire expected, such as distilled water mist type fire extinguishers with a minimum 2-A:C rating. [California Code of Regulations, Title 19, Division 1, §567.8] Installation Temperatures. Water- type (water, AFFF, FFFP) extinguishers shall not be installed in areas where temperatures are outside the range of 40°F to 120°F (4°C to 49°C). Other types shall not be installed in areas where temperatures are outside the range of -40°F to 120°F (-40°C to 49°C). Fire extinguishers shall not be exposed to temperatures outside of the range shown on the fire extinguisher label. Exceptions: 1. Where fire extinguishers are *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 11 of 47 installed in locations subject to temperatures outside these ranges, they shall be of a type approved and listed for the temperature to which they are exposed, or they shall be placed in an enclosure capable of maintaining the stipulated temperature range. 2. Fire extinguishers containing plain water only can be protected to temperatures as low as -40°F (-40°C) by the addition of an antifreeze stipulated on the extinguisher nameplate. Calcium chloride solutions shall not be used in stainless steel fire extinguishers. 3. Some fire extinguishers are approved or listed for use at temperatures as low as -65°F (-54°C). [California Code of Regulations, Title 19, Division 1, §574.1] Frequency of Inspection. Fire extinguishers shall be manually inspected when initially placed in service. Thereafter, extinguishers shall be manually inspected at least monthly by the building owner, occupant or his/her authorized agent, or electronically monitored. Fire extinguishers shall be inspected at more frequent intervals when circumstances require, as determined by the Authority Having Jurisdiction. [California Code of Regulations, Title 19, Division 1, §574.2] Inspection Procedures. (a) In addition to California Code of Regulations, Title 19, Division 1, Section *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 12 of 47 574.1, fire extinguishers shall be manually inspected in accordance with this section if they are located where any of the following conditions exist: (1) High frequency of fires in the past. (2) Extra (high) hazard areas. (3) Location that makes fire extinguishers susceptible to mechanical or physical damage. (4) Exposure to abnormal temperatures or corrosive atmospheres. (b) Manual inspection of extinguishers shall include a check of at least the following items: (1) Located in designated place. (2) No obstruction to access or visibility. (3) Operating instructions on nameplate legible and facing outward. (4) Safety seals and tamper indicators not broken or missing. (5) Examine for obvious physical damage, corrosion, leakage or clogged nozzle. (6) Pressure gauge reading or indicator in the operable range or position. (7) Fullness determined by weighing or hefting. (8) For wheeled units, the condition of tires, wheels, carriage, hose and nozzle shall also be checked. (9) For nonrechargeable extinguishers using push-to-test pressure indicators, test the indicator. (c) Electronic monitoring shall include monitoring of the following items: (1) Located in the designated place. *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 13 of 47 (2) No obstruction to access or visibility. (3) Pressure gauge reading or indicator in the operable range or position. [California Code of Regulations, Title 19, Division 1, §567.1] Operating Conditions. Portable extinguishers shall be maintained in a fully charged and operable condition, and kept in their designated places at all times when they are not being used. [California Code of Regulations, Title 19, Division 1, §574.3] Corrective Action. When an inspection of any extinguisher reveals a deficiency in any of the conditions listed in Title 19, Division 1, Sections 574.2(b)(c), immediate corrective action shall be taken. [California Code of Regulations, Title 19, Division 1, §574.4] Nonrechargeable Extinguishers. When an inspection of any nonrechargeable fire extinguisher reveals a deficiency in any of the conditions listed in (3), (4), (5), (6), (7) or (9) of Title 19, Division 1, Section 574.2(b), it shall be discharged and removed from service. Exception: Nonrechargeable extinguishers containing a halon agent shall be removed from service, not discharged, and returned to the manufacturer or local fire extinguisher distributor having the capability of recovering the halon agent. [California Code of Regulations, Title 19, Division 1, §575.10] Out of Service. Fire *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 14 of 47 extinguishers removed from service for maintenance or recharge shall be replaced by fire extinguishers suitable for the type of hazard protected and shall be of at least equal rating. [California Code of Regulations, Title 19, Division 1, §591.5] Replacement Extinguishers. Portable fire extinguishers shall not be removed from the premises for hydrostatic testing or any other purpose, without first replacing the extinguisher with a unit rated for the hazard being protected. The customer’s original unit shall be returned within 60 calendar days. [California Code of Regulations, Title 19, Division 1, §596.7(a) and (b)] Removal of Tag. (a) No person shall remove any tag, collar or label required by Title 19, Division 1, Chapter 3, Article 9 from a portable fire extinguisher except when service is performed. (b) No person shall deface, modify or alter any tag collar or label required by California Code of Regulations, Title 19, Division 1, Chapter 3, Article 9 to be attached to any portable fire extinguisher. [California Code of Regulations, Title 19, Division 1, §574.5(a) through (c)] Inspection Record Keeping. (a) The fire extinguisher owner shall maintain records of all fire extinguishers inspected, including those extinguishers that were found to *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 15 of 47 require corrective actions. Records shall be maintained until next required maintenance. (b) At least monthly, the date the manual inspection was performed and the initials of the person performing the inspection shall be recorded on a tag or label attached to the fire extinguisher, or an inspection checklist maintained on file, or an electronic system (e.g., bar coding) that provides a permanent record. (c) Fire extinguishers being inspected via electronic monitoring, whereby the extinguisher causes a signal at a control unit when a deficiency in any of the conditions listed in California Code of Regulations, Title 19, Division 1, Section 574.2(c) occurs, shall provide record keeping in the form of an electronic event log at the control panel. 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life- saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. Knox Box Upon completion of construction: -Update the Knox Box with all new master keys for buildings receiving new lock hardware. Reference: CFC Section 506.1 08/18/2026 08/10/2026 12:00:30 1013.1 Where required. Exits and exit access doors shall be marked by an approved exit Means of Egress – Emergency Lighting and Exit Signs: 10/08/2026 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 16 of 47 sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that any point in an exit access corridor or exit passageway is within 100 feet (30 480 mm) or the listed viewing distance of the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1.Exit signs are not required in rooms or areas that require only one exit or exit access. 2.Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. 3.Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3 or R-3.1. 4.Exit signs are not required where inmates are housed or held in dayrooms, sleeping rooms or dormitories in occupancies in Group I-3. 5.In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit The following deficiencies were observed: -Non-operational emergency exit lighting. -Missing exit signage due to construction. -Inoperative emergency "bug-eye" lighting fixtures. -Missing exit signage in classrooms. -Exit signs removed during construction have not been reinstalled. Required Correction: Repair or replace all inoperative emergency lighting and reinstall all required exit signs. Verify that all required exit signage and emergency lighting are operational before the beginning of the 2026–2027 school year. 2025 CFC References: CFC 1002.1 – Maintenance of Means of Egress CFC 1003.1 – Applicability CFC 1008.1 – Means of Egress Illumination CFC 1013.1 – Where Required, Exit Signs CFC 1013.3 – Illumination CFC 1013.5 – Internally Illuminated Exit Signs The 2025 code requires means of egress to be maintained and requires approved exit signs to be readily visible along the required egress path. Exit signs must also remain illuminated. *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 17 of 47 signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. 603.4 Working space and clearances. Working space around electrical equipment shall be provided in accordance with Section 110.26 of the California Electrical Code for electrical equipment rated 1,000 volts or less, and Section 110.32 of the California Electrical Code for electrical equipment rated over 1,000 volts. The minimum required working space shall be not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the minimum working space shall be not less than the width of the equipment. Storage of materials shall not be located within the designated working space. 9. Electrical Safety -Remove combustible storage from electrical rooms. -Maintain required working clearances around all electrical equipment. Reference: CFC Section 603.4 08/18/2026 08/10/2026 11:52:26 703.1 Maintaining protection. Materials and firestop systems used to protect membrane and through penetrations in fire- resistance-rated construction and construction installed to resist the passage of smoke shall be maintained. The materials and firestop systems shall be securely attached to or bonded to the construction being 6. Building Maintenance – Missing Ceiling Tiles: Missing ceiling tiles were observed throughout classrooms and other occupied spaces. Required Correction: Replace missing ceiling tiles and restore affected ceiling assemblies to their approved condition to maintain required fire- 08/26/2026 08/26/2026 12:28:39 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 18 of 47 penetrated with no openings visible through or into the cavity of the construction. Where the system design number is known, the system shall be inspected to the listing criteria and manufacturer’s installation instructions. resistance characteristics and minimize smoke migration. 2025 CFC References: CFC 703.1 – Maintenance of Fire- Resistance-Rated Construction 3303.1.1 Components of site safety plans. Site safety plans shall include the following as applicable: 1.Name and contact information of site safety director. 2.Documentation of the training of the site safety director and fire watch personnel. 3.Procedures for reporting emergencies. 4.Fire department vehicle access routes. 5. Location of fire protection equipment, including portable fire extinguishers, standpipes, fire department connections and fire hydrants. 6.Smoking and cooking policies, designated areas to be used where approved, and signage locations in accordance with Section 3305.8. 7.Location and safety considerations for temporary heating equipment. 8.Hot work permit plan. 9.Plans for control of combustible waste material. 10.Locations and methods for storage and use of flammable and combustible liquids and other hazardous materials. 11.Provisions for site security. 12.Changes that Construction Fire Safety -Multiple construction projects were underway throughout the campus. The following requirements shall be maintained during construction: -Keep construction access gates secured when not in use. -Maintain temporary fencing separating construction areas from occupied campus areas. -Prevent unauthorized student access to construction zones. -Continue maintaining fire department access where required. Reference: CFC Section 3303.1.1 08/18/2026 08/10/2026 11:56:26 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 19 of 47 affect this plan. 13.Other site-specific information required by the fire code official. 603.6 Extension cords. Extension cords shall not be a substitute for permanent wiring and shall be listed and labeled in accordance with UL 817. Extension cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. Extension cords marked for indoor use shall not be used outdoors. 12. Extension Cords -Multiple temporary extension cords were observed in active construction areas. -These temporary wiring methods shall be removed upon completion of construction activities. Reference: CFC Section 603.6 08/18/2026 08/10/2026 13:20:16 901.6 Inspection, testing and maintenance. Fire protection and life safety systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection and life safety systems and equipment shall be inspected, tested and maintained or removed in accordance with Section 901.8. All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by these regulations shall be maintained in an operable condition at all times in accordance with this code and California Code of Regulations, Title 19, Division 1. Upon disruption or 1. Fire Alarm System: Due to active construction, the Fire Alarm Control Panel (FACP) displayed multiple supervisory/trouble conditions. Full system operation could not be verified because construction activities may have affected system components. Required Correction: Upon completion of construction, have a qualified fire alarm contractor test the complete system and verify that it has been restored to normal operation. Provide the Fire Department with testing documentation and upload the applicable report to The Compliance Engine. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance 08/26/2027 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 20 of 47 diminishment of the fire protective qualities of such equipment, material or systems, immediate action shall be instituted to affect a reestablishment of such equipment, material or systems to their original normal and operational condition. [California Code of Regulations, Title 19, Division 1, §1.14] Maintenance. Every fire alarm system or device, sprinkler system, fire extinguisher, fire hose, fire-resistive assembly or any other fire safety assembly, device, material or equipment installed and retained in service in any building or structure subject to California Code of Regulations, Title 19, Division 1 regulations shall be maintained in an operable condition at all times in accordance with California Code of Regulations, Title 19, Division 1 regulations and with their intended use. [California Code of Regulations, Title 19, Division 1, §3.24] Maintenance of Equipment. All fire alarm systems, fire detection systems, automatic sprinkler or extinguishing systems, communication systems, and all other equipment, material or systems required by California Code of Regulations, Title 19, Division 1 shall be maintained in an operable condition at all times. Upon disruption or diminishment of the fire protective qualities of such equipment, material or systems, The 2025 CFC specifically requires fire protection and life safety systems to be maintained in an operative condition and requires fire alarm systems to be tested and maintained in accordance with NFPA 72. 2. Private Fire Hydrants / Fire Department Connections: Private fire hydrant(s) are listed as deficient in The Compliance Engine. Required Correction: The contractor of record shall correct all deficiencies and upload a compliant inspection report to The Compliance Engine. Note: Construction plans indicate a new OS&Y/double-check assembly was installed on the west side of the property, with modifications to the domestic and fire service lines and removal of three existing FDCs. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance Note: Final verification of proper installation, accessibility, and operational readiness shall be completed following construction. 5. Building G – Sprinkler Riser Room: The north sprinkler riser room was missing the required hydraulic calculation plate. Required Correction: *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 21 of 47 immediate action shall be instituted to affect a reestablishment of such equipment material or systems to their original normal and operational condition. [California Code of Regulations, Title 19, Division 1, §904(a)] Required Inspection, Testing and Maintenance Frequencies. (a) All automatic fire extinguishing systems, including systems installed as an alternate to other building requirements, shall be inspected, tested and maintained in accordance with the following frequencies. Local authorities may require more frequent inspection, testing and maintenance and additional procedures. [California Code of Regulations, Title 19, Division 1, §904(a)(1)] Required Inspection, Testing and Maintenance Frequencies. (1) Water-based fire protection systems shall be inspected, tested and maintained in accordance with the frequencies required by NFPA 25 (2011 edition) including Annexes A, B, C, D, E, F and G as amended by the State of California. (Published as NFPA 25, 2013 California Edition.) [California Code of Regulations, Title 19, Division 1, §904(b)] Required Inspection, Testing and Maintenance Frequencies. (b) When proof of the installation date of standpipe systems or automatic fire Provide and properly install the required hydraulic design information/calculati on plate at the sprinkler riser. 2025 CFC References: CFC 901.6 – Inspection, Testing and Maintenance NFPA 13, as referenced by CFC Table 901.6.1 – Hydraulic Design Information Sign Note: The sprinkler system shall retain the required hydraulic design information for identification and maintenance purposes. *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 22 of 47 sprinkler systems cannot be furnished, such systems shall receive initial testing and maintenance by July 1, 1985. [California Code of Regulations, Title 19, Division 1, §904.2(a)] Testing and Maintenance Requirements. (a) All testing and maintenance on automatic fire extinguishing systems in accordance with Health & Safety Code Section 13195 shall be performed by those licensed in accordance with Health and Safety Code Section 13196.5. Exceptions: (1) The State Fire Marshal may waive, in writing, licensing of fire departments which conduct fire sprinkler and standpipe system testing and maintenance. (2) Service on fire alarm systems and industrial systems as specified in Health and Safety Code Sections 13196.5(b) and (c) may be conducted without a license. (3) Testing and maintenance on automatic fire extinguishing systems exempted in writing by the State Fire Marshal, when the building owner or occupant has the staff and equipment to conduct testing and maintenance. [California Code of Regulations, Title 19, Division 1, §904.2(b)] Testing and Maintenance Requirements. (b) Any testing and maintenance of automatic fire extinguishing systems shall be *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 23 of 47 performed in accordance with these requirements. Exceptions: (1) The State Fire Marshal may waive, in writing, the requirement that testing and maintenance be performed in accordance with these requirements when a licensee can demonstrate that a system cannot functionally be tested and maintained in accordance with the California Code of Regulations, Title 19, Division 1, Chapter 5. (2) If at any time a licensee encounters a specialized or modified system which cannot be tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5, the licensee shall contact the State Fire Marshal and test and maintain the system as directed. (A) The intent of this section is to cover automatic fire extinguishing systems as originally designed, installed and approved by the Authority Having Jurisdiction. It is not, however, intended to require that such systems be upgraded to current adopted standards. [California Code of Regulations, Title 19, Division 1, §904.2(h)] Testing and Maintenance Requirements. (h) At the time of testing and maintenance, building management shall be consulted to avoid unnecessary disturbance of normal building operation. [California Code of *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 24 of 47 Regulations, Title 19, Division 1, §904.2(i)] Testing and Maintenance Requirements. (i) The licensee shall contact the local fire authority having jurisdiction prior to testing and maintenance of a system when required by the local fire authority having jurisdiction to do so. 912.7 Inspection, testing and maintenance. Fire department connections shall be periodically inspected, tested and maintained in accordance with California Code of Regulations, Title 19, Division 1, Chapter 5. Records of inspection, testing and maintenance shall be maintained. Newly Installed OS&Y / Double-Check Assembly: The new OS&Y/double-check assembly requires completion of the Fire Department Connection installation. Required Correction: Install the approved FDC connection, provide approved protective cap covers, and install the required chain and lock on the double- check/OS&Y valve assembly. 2025 CFC References: CFC 912.7 – Inspection, Testing and Maintenance 08/26/2026 08/26/2026 12:29:26 906.1 Where required. Portable fire extinguishers shall be installed in all of the following locations: 1.In new and existing Group A, B, E, F, H, I, L, M, R-1, R-2, R-2.1, R-2.2, R-3.1, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1- A:10-B:C. 2.Within 30 feet (9144 mm) distance Portable Fire Extinguishers: Portable fire extinguishers have been annually serviced but were not reinstalled in their designated locations. Required Correction: Reinstall all portable fire extinguishers in their designated and approved locations before occupancy. 2025 CFC References: CFC 906.1 – Where Required Note: The 2025 CFC requires portable fire extinguishers to be conspicuously 08/26/2026 08/26/2026 12:31:01 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 25 of 47 of travel from commercial cooking equipment and from domestic cooking equipment in Group R-2 college dormitory occupancies. 3.In areas where flammable or combustible liquids are stored, used or dispensed. 4.On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3316.1. 5.Where required by the sections indicated in Table 906.1. 6.Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. 7.Large and small family day-care homes shall be equipped with a portable fire extinguisher having a minimum 2-A:10-B:C rating. 8.Where required by California Code of Regulations, Title 19, Division 1. 9.Within 30 feet (9144 mm) of domestic cooking equipment located in a Group I-2. [California Code of Regulations, Title 19, Division 1, §3.29(a) through (d)] Portable Fire Extinguishing Equipment. (a)General. Portable fire extinguishers conforming to the requirements of California Code of Regulations, Title 19, Division 1, Chapter 3, shall be installed and maintained in accordance with guides established therein. (b)Special Coverage. Additional Class A, B and C units of located, readily accessible, and installed on approved hangers or brackets. *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 26 of 47 adequate extinguishing potential shall be provided for any other hazard, as determined by the enforcing agency. (c)Group A Occupancies. (1)One additional Class 2-A unit shall be provided in Group A Occupancies as follows: (A)On each side of the stage or platform. Exception: Platforms 1000 square feet or less in area need have only one such extinguishing unit. (B)On each side of every fly gallery. (C)In basements beneath the stage or platform. (D)In every hallway or passageway leading to a dressing room. (E)In every property room, carpenter shop or similar workroom. (2)Not less than one 10-B:C unit (not less than 4-B:C for existing extinguishers in existing occupancies) shall be provided: (A)For each motor and fan room. (B)Adjacent to each switchboard on the stage or platform. (C)For each motion picture machine in projection rooms. Exception: One 20- B:C unit (not less than 8-B:C for existing extinguishers in existing occupancies) in each projection room may be accepted as providing substantially equal protection. (3)The enforcing agency may allow modifications or deviations relative to the number and location of portable fire extinguishers as required by this section provided such authority finds that the basic intent of *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 27 of 47 this section and the ease of accessibility to extinguishers is otherwise achieved. (d)Group R-2.1, R-3.1 and R-4 Occupancies. In Group R-2.1, R-3.1 and R-4 occupancies, a continuously attached garden hose, equipped with a water flow control nozzle, may be provided in lieu of one or more required fire extinguishers when acceptable to the enforcing agency. The location and length of such hose shall be as designated or approved by the enforcing agency. NOTE: It is recommended that, wherever possible, portable fire extinguishers be located adjacent to manual fire alarm sending stations. [California Code of Regulations, Title 19, Division 1, §565(a)] Selection of Fire Extinguishers. (a)The selection of extinguishers for a given situation shall be determined by the authority having jurisdiction in accordance with adopted codes or ordinances. The character of the fires anticipated, the construction and occupancy of the individual property, the vehicle or hazard to be protected, ambient-temperature conditions and other factors shall be considered. The number, size, placement and limitations of use of extinguishers required shall be determined by using California Code of Regulations, Title 19, Division 1, Sections 567 through 573. Exception: Portable *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 28 of 47 fire extinguishers are not required at normally unmanned Group U occupancy buildings or structures where a portable fire extinguisher suitable to the hazard of the location is provided on the vehicle of visiting personnel. 907.10 Smoke alarm maintenance. Smoke alarms shall be tested and maintained in accordance with the manufacturer’s instructions. Smoke alarms shall be replaced when they fail to respond to operability tests, or when they exceed 10 years from the date of manufacture, unless an earlier replacement is specified in the manufacturer’s published instructions. Welding Shop: The welding shop requires additional fire/life safety corrections. Required Correction: Install a smoke detector in the classroom. Replace the old/recalled natural gas connectors connected to the appliance located on the workbench. 2025 CFC References: CFC 907.10 – Smoke Alarm Maintenance, as applicable Note: Recalled or damaged equipment and components shall be corrected or replaced as required. The 2025 CFC requires unsafe electrical conditions to be abated and damaged or modified equipment constituting a hazard to be repaired or replaced. 10/08/2026 605.1 General. The design, construction, installation, operation, alteration, repair and maintenance of nonportable gasfired appliances and systems shall comply with the California Plumbing Code. The design, construction, installation, operation, alteration, repair and maintenance of nonportable solid Building C – Mechanical Room: Gas appliances previously installed in the mechanical room are no longer in service/use. Required Correction: Install appropriate identification/signage for gas appliances that have been removed from service or are no longer in use, as applicable, and ensure unused 10/08/2026 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 29 of 47 fuel-fired and oil- fired appliances and systems shall comply with the provisions of this section and the California Mechanical Code. The construction and use of portable fuelfired appliances not connected to a fixed fuel piping system, such as blow torches, melting pots and weed burners, shall comply with this section. gas equipment is safely secured or removed. 2025 CFC References: CFC 605.1 – General, Fuel-Fired Appliances Note: The 2025 CFC prohibits continued operation of appliances whose operation has been discontinued or ordered discontinued unless authorized by the fire code official. 603.2.2 Open electrical terminations. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Annex Building – Basketball Gym: Exposed electrical outlets were observed. Required Correction: Install approved covers over all exposed electrical outlets and electrical boxes. 2025 CFC References: CFC 603.2.2 – Open Electrical Terminations The 2025 CFC specifically prohibits open junction boxes and open-wiring splices and requires approved covers for electrical and outlet boxes. 08/26/2026 08/26/2026 12:26:39 Inspection Documents *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 30 of 47 Title: image *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 31 of 47 Title: image *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 32 of 47 Title: image *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 33 of 47 Title: image *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 34 of 47 Title: image *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 35 of 47 Title: Laguna Middle School @ Annual Cover page 7.16.26 GDA *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 36 of 47 Title: Laguna Middle School @ Annual Cover page 7.16.26 GDA (1) *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 37 of 47 Title: Laguna Middle School @ Annual FA report 7.16.26 GDA *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 38 of 47 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 39 of 47 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 40 of 47 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 41 of 47 Title: IMG_2027 Title: IMG_2028 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 42 of 47 Title: IMG_2029 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 43 of 47 Title: IMG_2030 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 44 of 47 Title: IMG_2031 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 45 of 47 Title: IMG_2032 *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court.Page 46 of 47 Title: Laguna Annual Drill Log 25-26 Violation Documents *Please note: If a third inspection is required due to non-compliance, a fire-inspection fee of $271 may be charged for that inspection, and every inspection thereafter until compliance is obtained. Failure to comply may result in a misdemeanor citation and an appearance by you in court. Page 47 of 47